Relay Outputs

Reference Manual

Rosemount 2410

300530EN, Rev BA September 2012

Relay Outputs

There are two optional relay outputs. You can choose Normally Open (NO) or Normally Closed (NC) by setting a switch as described in “Relay Output Configuration” on page 6-15.

NO and NC refers to the contact position when a relay is deenergized. This is also referred to as the Alarm state. The terminology can be summarized as follows:

Table 3-9. Designation of relay

contact positions

Normally Closed (NC)

Normally Open (NO)

 

Deenergized

Energized

Deenergized

Energized

 

Closed

Open

Open

Closed

 

Not active

Active

Not active

Active

 

Alarm (Reset)

Normal

Alarm (Reset)

Normal

NOTE!

Ensure that maximum current through the relays does not exceed the specifications in Appendix A: Reference Data.

See “Relay Output” on page C-6in Appendix C: Advanced Configuration for information on how to configure the relay source signal, set points etc. for the Rosemount 2410 Tank Hub.

3-26

Section 3. Installation