Reference Manual
Rosemount 2410
300530EN, Rev BA September 2012
Analog input/output electrical | Analog Input |
characteristics | Maximum number of input channels: 1 |
| Input Current range: 0 - 23 mA |
| Configurable Min and Max alarm limits. |
| |
| Max input voltage (Passive IS and |
| Output voltage (Active): |
| |
| IS: 21 ±2.0V (open loop); 18.8 ±2.0V@3,75 mA; 8.2 ±2.0V @ 21.75 mA |
| See 'Product Certifications' for IS parameters |
| HART Master: |
| Maximum 5 HART Slave Devices (Passive). |
| Maximum 3 HART Slave Devices (Active ). |
| Analog Output: |
| Maximum number of output channels: 1 |
| Output range: |
| SW Configurable High and Low Alarm Limits. |
| Separate SW Configurable Alarms for process failures and HW failure. |
| Low voltage and invalid loop current detection. |
| |
| Max input voltage (Passive IS and |
| Output voltage (Active): |
| |
| IS: 21 ±2.0V (open loop); 20.8 ±2.0V@3,75 mA; 10.2 ±2.0V @ 21.75 mA |
| See Product Certifications for IS parameters |
| HART slave configurable HART 5 or HART7(4) (HART 5 default) |
Integral display output variables | The integral digital |
| strength, volume (TOV), liquid average temperature, |
| temperature, ambient temperature, free water level, vapor pressure, liquid pressure, air |
| pressure, observed density, reference density, and flow rate |
Display output units(5) | Level, free water level, and ullage: meter, millimeter, feet, or imperial 1/16 |
| Level rate: meter/second, meter/hour, feet/second, or feet/hour |
| Flow rate: meter3/hour, liter/minute, barrel/hour, or US gallon/hour |
| Total Observed Volume (TOV): meter3, liters, barrel, or US gallon |
| Temperature: °F, °C, or °K |
| Pressure: psi, psiA, psiG, bar, barA or barG, atm, Pa, or kPa |
| Density: kg/m3, °API, or 60/60DegF |
| Signal strength: mV |
Configuration tools | Rosemount TankMaster |
Autoconfiguration support | Yes (Tankbus addressing) |
Electric |
|
Power supply (nominal values) | |
Power consumption | Max. 20 W depending on configuration |
Cable entry (connection/glands) | |
| IS side: Two ½ - 14 NPT entries for cable glands or conduits |
| Three metal plugs to seal any unused ports are included in the delivery. |
| Optional: |
| • M20 x 1.5 and M25 x 1.5 conduit / cable adapter |
| • Cable glands in metal (½ - 14 NPT and |
| • |
Tankbus cabling | |
Power and relay cabling | |
Maximum Tankbus cable lengths | Depends on cable. See “Cable Selection for the Tankbus” on page |
| parameters. |
Yes (to be disconnected if required) |
Appendix A. Reference Data |