6.2.13Loading the Default Database

Reference Manual

Rosemount 2410

300530EN, Rev BA September 2012

6.2.13Loading the Default Database

The various configuration parameters of the 2410 Tank Hub is stored in a Holding Register database. The Holding Register factory setting is stored in the default database. TankMaster WinSetup offers the option to load the default database. This may be useful if, for example, you would like to try out new database settings and then be able to reload the original factory settings.

In case error messages appear or other problems occur concerning the database, troubleshooting the cause of these problems is recommended before loading the default database.

It is recommended that the current database is backed up before the Default Database is loaded. See “Configuration Backup” on page 6-5for information on how to save the current database.

NOTE!

The communication adress of the device remains unaltered when the default database is loaded.

NOTE!

When the default database is loaded to the 2410 Tank Hub measurement units are reset to Metric Units.

To load the default database:

1.Select the desired device icon in the TankMaster WinSetup workspace window.

2.Click the right mouse button and choose the View Holding Register option.

3.Choose the All option and type 65510 in the Start Register input field. Type the desired number of registers to be displayed in the Number of Registers field and click the Read button.

4.Type 65510 in the Value input field.

5.Click the Apply button to load the default database.

6.Finish by clicking the Close button.

7.Verify that measurement units are compatible with the current host system configuration.

6-16

Section 6. Service and Troubleshooting

Page 90
Image 90
Emerson Process Management Rosemount 2410 Loading the Default Database, To load the default database, Reference Manual