Rosemount
Reference Manual
Tank Hub
Page
Rosemount
Rosemount Tank Hub
Spare Parts
Page
SECTION 1 Introduction SECTION 2 Overview SECTION 3 Installation
Table of Contents
SECTION 4 Configuration
APPENDIX A Reference Data APPENDIX B Product Certifications
SECTION Service and Troubleshooting
APPENDIX C Advanced Configuration
SECTION 5 Operation
TOC-3
TOC-4
page
1.1 SAFETY MESSAGES
Section
Introduction
1.2 SYMBOLS
Appendix C Advanced Configuration
Section 3 Installation
Section 4 Configuration
Section 6 Service and Troubleshooting
1.4 TECHNICAL DOCUMENTATION
1.6 PRODUCT RECYCLING/DISPOSAL
1.7 PACKING MATERIAL 1.7.1 Reuse and Recycling 1.7.2 Energy recovery
Rosemount
2.1 INTRODUCTION
Overview
Rosemount
2.1.1 Communication
THUMAdapter
Smart Wireless
2.2 COMPONENTS
1 See documents IEC 61158-2 and IEC/TS
2.3 SYSTEM OVERVIEW
TRANSFER / INVENTORY TANK GAUGING
NON-HAZARDOUS AREA HAZARDOUS AREA
CONTROL CUSTODY
HAZARDOUS AREA
NON-HAZARDOUS AREA
Rosemount 5900S Radar Level Gauge
TankMaster HMI Software
Rosemount 2160 Field Communication Unit
Rosemount 2410 Tank Hub
Rosemount 2230 Graphical Field Display
Rosemount 5300 Guided Wave Radar
Rosemount 5400 Radar Level Transmitter
Rosemount 2240S Multi-Input Temperature Transmitter
Rosemount
Mount the See “Mechanical Installation” on page Wire the
2.4 INSTALLATION PROCEDURE
Installation
3.1 SAFETY MESSAGES
3.2 INSTALLATION CONSIDERATIONS
Bracket
3.3 MECHANICAL INSTALLATION
3.3.1 Pipe Mounting
1 - 2 inches Bracket
Ø 9 mm
3.3.2 Wall Mounting
94 mm
70 mm
3.4.2 Power Supply 3.4.3 Cable Selection for Power Supply
3.4 ELECTRICAL INSTALLATION
3.4.1 Cable Entries
3.4.4 Grounding 3.4.5 Cable Selection for the Tankbus
Shield Wire Ground
Grounding - Foundation Fieldbus
2 Maximum five Rosemount 5300 or 5400 level transmitters
3.4.6 Power Budget
Power consumption
Field device
Termination
3.4.7 Tankbus
Fieldbus Segment Design
resistance
Typical installation
Typical loop
Maximum Current
Example
Segment
5400 Radar Level
Tankbus Segment Coupler
Trunk IN
Examples
Trunk OUT
Spur60 m
Segment coupler with active terminator end of trunk
3-14
enabled on the
3.4.8 Typical Installations
2240S Multi-input Temperature
is connected to the
Pressure transmitter
Secondary 2410 Tank Hub
Secondary Tank Hub
Segment coupler with integrated bus terminator
644 Temperature
2240S Multi-input
Rosemount
Reference Manual
Rosemount
Reference Manual
Rosemount
TRL2 Bus
3.4.9 Cabling for the TRL2/RS485 Bus
RS485 Bus
Terminal block Ground screws
3.4.10 Non-IS Connection
Non-IS compartment Wiring with drip loop Ground screw
Safety locking screw Cable entries
Stripping length 10 mm Conductor cross-sectional area, see Table
Conductor Recommendations
Conductor
Terminal block
3-24
Secondary Communication Bus
Power Supply
3.4.11 Non-IS Terminal Block
Primary Communication Bus
Relay Outputs
XP/Exd/Exe Ground screw Ground screws SIL Relay
Non-IS Terminal Block for SIL Safety Systems
SIL Alarm Relay B
SIL Alarm Relay A
IS compartment Wiring with drip loop Terminal block Ground screws
3.4.12 IS Connection
Cable entries
Tankbus
3.4.13 Intrinsically Safe Terminal Block
Optional Secondary Bus
IS Terminal Block for SIL Safety Systems
Intrinsically safe Tankbus
3.4.14 Wiring Diagrams
ROSEMOUNT
Terminal block on intrinsically safe side
3-32
Rosemount
Radar Level Gauge
3-34
4.1 SAFETY MESSAGES
Configuration
Rosemount 2410 Series
4.2 INTRODUCTION
4.3 CONFIGURATION TOOLS
Device Tags
4.4 BASIC CONFIGURATION OF A ROSEMOUNT
Communication
Tank Database
4.6 CONFIGURATION USING TANKMASTER WINSETUP
4.5 ADVANCED CONFIGURATION
See Appendix C Advanced Configuration for more information
4.6.2 Advanced Configuration
4.6.1 Installation Wizard
Install New
2410Level
4.6.3 FCU 2160 Configuration
2410Temp is automatically added
Operation
5.1 SAFETY MESSAGES
measurement unit Write protection switch
5.2 INTEGRAL DISPLAY
Measurement value Toggling between measurement variable and
Description
Variable
Presentation on display
Example
5.3 START-UP INFORMATION
Error
“ERROR” indication Fail/Error code
Code
occurs, the Error LED flashes a sequence that corresponds to
5.5 LED
5.5.1 LED Start-Up Information
Error LED Red Status LED Yellow Power On LED Green
Seconds
5.5.2 Error LED
Error LED Red
Other memory error
5.6 SPECIFYING DISPLAY VARIABLES
6.1 SAFETY MESSAGES
Section 6 Service and Troubleshooting
6.2.1 Viewing Input and Holding Registers
6.2 SERVICE
Predefined All
6.2.2 Editing Holding Registers
1. Start the TankMaster WinSetup program
6.2.3 Device Live List
A removable tag provided with the device lets you identify the
6.2.4 Configuration Backup
6.2.5 Configuration Recovery
The Configure button lets you open the Configure Diagnostic Registers window, allowing you to change the list of registers to be displayed in the View Diagnostic Registers window
6.2.6 Diagnostics
6.2.7 Device Software Upgrade
Rosemount
Write Protect
6.2.8 Write Protection
Write protection switch
6.2.9 Write Protection Switch
HR3868 HR3994 HR3976
Average Temperature Total Observed Volume Observed Density
Simulation Parameter
Simulation Holding Register
Simulation mode active
Advanced Simulation
6.2.11 Testing the Relays
Relay K2 NC - NO
6.2.12 Relay Output Configuration
Front cover
Relay K1 NC - NO
To load the default database
6.2.13 Loading the Default Database
6.2.14 Logging Measurement Data
Possible cause
6.3 TROUBLESHOOTING
Symptom
See the Raptor System Configuration Manual
Check Device Status input register, see “Device Status”
Check that the total current consumption of the devices
Check that there are no multiple shield grounding points
open the FCU Properties/Slave Database window
See the Rosemount 5900S Reference Manual
6-22
Advanced Parameter Source Configuration tab. Check
WinSetup Tank View window, and
In TankMaster Winsetup, right-click the ATD device icon
The device is write protected with a switch
6.3.1 Device Status
Double-click the Value field to open the Expanded Bitfield window
6.3.2 Warning Messages
Source Configuration tab
application software. Try to reprogram the
6.3.3 Error Messages
6-26
Rosemount
6-28
page A-1
A.1 SPECIFICATIONS
Appendix A
Reference Data
Analog input/output electrical
Housing material
254 mm 164 mm 193 mm
A.2 DIMENSIONAL DRAWINGS
For connection to a 3rd party system For connection to a 3rd party system
A.3 ORDERING INFORMATION
6 Requires Secondary Fieldbus Pos 5, code 0 or F
1 Requires Secondary Fieldbus Pos 5, code A-F, W, 0
2 Requires Primary Fieldbus Pos 4 code R or
4 Requires Relay Output Pos 6 code 0 or F
Appendix B Product Certifications
B.1 SAFETY MESSAGES
B.2 EU CONFORMITY
B.3 HAZARDOUS LOCATIONS CERTIFICATIONS
E5 FISCO Power Supply
B.3.1 Factory Mutual US Approvals
HART/4-20 mA ENTITY IS I/O Option
B.3.2 Factory Mutual Canadian Approvals
E6 FISCO Power Supply
Rosemount
B.3.3 European ATEX Directive Information
FISCO Power Supply
B.3.4 IECEx Approval
B-10
B-11
B.4 APPROVAL DRAWINGS
B-12
C.1 SAFETY MESSAGES
Appendix C Advanced Configuration
Rosemount
C.2 ADVANCED CONFIGURATION IN WINSETUP
Configuration window
C.3 PRIMARY BUS
1. In the Configuration field, change from Standard to Non Standard
Figure C-3. Secondary Bus Configuration window
C.4 SECONDARY BUS
Hysteresis
Using two/three relay zones
C.5 RELAY OUTPUT
First and second set points
Source
Switch Delay
Virtual Relay States
Virtual Relay Output
Normally Closed
Relay output configuration
Normally Open
Relay Zones
C-10
C.6 HYBRID DENSITY CALCULATION
C-11
C-12
Configuration
C.6.1 Hybrid Density
1. Open the 2410 Tank Hub/Configuration window
C-13
Strapping Table
C.7 VOLUME CONFIGURATION
C-14
Note the Volume Offset is added when predefined tank
Holding and Input Registers for Volume Configuration
C-16
Tank measurement variable in which the result is stored
C.8 ARITHMETIC OPERATIONS
Rosemount
C-19
C.8.1 Delta Level Calculation
C-20
Numerics
Index
Index-2
Secondary Communication Bus
Page
Monel is a trademark of International Nickel Co
FOUNDATION is a trademark of the Fieldbus Foundation
All other marks are the property of their respective owners