HART/4-20 mA ENTITY IS I/O Option

Active Current Loop XP-AIS CL I, DIV. 1 GP C & D Ex de[ia IIC] IIB

Uo = 23.1 V, Io = 95.3 mA, Po = 550 mW Group IIC: Co 0.14 μF, Lo 3.9 mH Group C, IIB: Co 1.0 μF, Lo 15 mH Group D, IIA: Co 3.67 μF, Lo 33 mH

Passive Current Loop

Ex de[ia IIC] IIB

Ui = 30.0 V, Ii = 300 mA, Ci = 0 μF, Li = 0 mH

Ambient Temperature Limits: -50 °C to +70 °C Temperature Code T4

Install per Control Drawing 9240040-901