6.2.14Logging Measurement Data

Reference Manual

300530EN, Rev BA September 2012

Rosemount 2410

6.2.14Logging Measurement Data

The Rosemount 2410 supports logging of diagnostic registers. This function is useful for verifying that the gauge works properly. The logging function can be accessed by using the TankMaster WinSetup program. To start logging do the following:

1.Start the TankMaster WinSetup program.

2.Select the Rosemount 2410 Tank Hub icon in the WinSetup workspace.

3.Click the right mouse button and choose Logging:

4.The Manual mode lets you start logging at any time. In Automatic mode you have to specify a Start and Stop time.

5.The resulting log file will not exceed the size specified by the Max File Size parameter.

In automatic mode logging will proceed until the stop date and time is reached.

In manual mode logging will proceed until it is stopped by clicking the Stop button.

Logging will stop automatically when the number of log files is equal to the number given by the Max Log Files parameter.

6.The log file is stored as a plain text file and can be viewed in any word processing program. It is stored in the following folder: C:\Rosemount\Tankmaster\Setup\Log, where C is the disk drive where the TankMaster software is installed.

The log file contains the same input registers as the View Diagnostic Registers window, see “Diagnostics” on page 6-7.

You can change which input registers to be included in the log file by configuring the View Diagnostic Registers window, see the Raptor System Configuration Manual (Document No. 300510EN) for more information.

Section 6. Service and Troubleshooting