Table 7-19. Troubleshooting the

AI block

Symptom

Possible Causes

Recommended Actions

 

 

 

 

BLOCK_ERR reads OUT OF

1. AI Block target mode set to OOS.

 

SERVICE (OOS)

2. Resource Block OUT OF SERVICE.

 

BLOCK_ERR reads

1. Check CHANNEL parameter (see “CHANNEL” on

 

CONFIGURATION ERROR

page 5-39).

 

 

2. Check L_TYPE parameter (see “L_TYPE” on page 5-39).

 

 

3. Check XD_SCALE engineering units. (see “XD_SCALE

Bad or no level readings

 

and OUT_SCALE” on page 5-40.

(Read the AI “BLOCK_ERR” parameter)

BLOCK_ERR reads POWERUP

Download Schedule into block. Refer to host for downloading

 

 

procedure.

 

BLOCK_ERR reads BAD INPUT

1. Sensor Transducer Block Out Of Service (OOS).

 

 

2. Resource Block Out of Service (OOS).

 

No BLOCK_ERR but readings

1. Check XD_SCALE parameter.

 

are not correct. If using Indirect

2. Check OUT_SCALE parameter.

 

mode, scaling could be wrong

(see “XD_SCALE and OUT_SCALE” on page 5-40).

OUT parameter status reads

Out_ScaleEU_0 and EU_100

See “XD_SCALE and OUT_SCALE” on page 5-40.

UNCERTAIN and substatus reads

settings are incorrect.

 

EngUnitRangViolation

 

 

Mode will not leave OOS

Target mode not set

Set target mode to something other than OOS.

 

Configuration error

BLOCK_ERR will show the configuration error bit set. The

 

 

following are parameters that must be set before the block is

 

 

allowed out of OOS:

 

 

CHANNEL must be set to a valid value and cannot be left at

 

 

the initial value of 0.

 

 

XD_SCALE.UNITS_INDX must match the units in the

 

 

transducer block channel value.

 

 

L_TYPE must be set to Direct, Indirect, or Indirect Square

 

 

Root and cannot be left at the initial value of 0.

 

Resource block

The actual mode of the Resource block is OOS. See

 

 

Resource Block Diagnostics for corrective action.

 

Schedule

Block is not scheduled and therefore cannot execute to go to

 

 

Target Mode. Schedule the block to execute.

Process and/or block alarms will not work

Features

FEATURES_SEL does not have Alerts enabled. Enable the

 

 

Alerts bit.

 

Notification

LIM_NOTIFY is not high enough. Set equal to MAX_NOTIFY.

 

Status Options

STATUS_OPTS has Propagate Fault Forward bit set. This

 

 

should be cleared to cause an alarm to occur.

Value of output does not make sense

Linearization Type

L_TYPE must be set to Direct, Indirect, or Indirect Square

 

 

Root and cannot be left at the initial value of 0.

 

Scaling

Scaling parameters are set incorrectly:

 

 

XD_SCALE.EU0 and EU100 should match that of the

 

 

transducer block channel value.

 

 

OUT_SCALE.EU0 and EU100 are not set properly.

Cannot set HI_LIMIT, HI_HI_LIMIT,

Scaling

Limit values are outside the OUT_SCALE.EU0 and

LO_LIMIT, or LO_LO_LIMIT Values

 

OUT_SCALE.EU100 values. Change OUT_SCALE or set

 

 

values within range.

7-46

Page 176
Image 176
Emerson Process Management 5300 manual 00809-0100-4530, Rev BA July 19. Troubleshooting AI block