Reference Manual

00809-0100-4530, Rev BA July 2009

Rosemount 5300 Series

Analog Output Status

Analog Output Status messages that may appear on the Integral Display, on

 

 

the 375 Handheld Communicator, or in RRM are shown in Table 7-10:

Table 7-10. Analog Output

 

 

 

status.

 

 

 

 

Message

Description

Action

 

Not connected

 

Analog output hardware is not

 

 

 

 

connected.

 

 

Alarm Mode

 

The analog output is in Alarm Mode.

Check Error and Warning Messages

 

 

 

 

to find the reason for the Alarm.

 

Saturated

 

The analog output signal value is

No action needed.

 

 

 

saturated, i.e. equal to the saturation

 

 

 

 

value.

 

 

Multidrop

 

The transmitter is in Multidrop Mode.

This is the normal setting when a

 

 

 

The analog output is fixed at 4 mA.

device is used in Multidrop

 

 

 

 

configuration.

 

Fixed Current mode

The analog output is in fixed current

This mode is used when calibrating

 

 

 

mode.

the Analog Output channel.

 

PV out of Limits

 

The Primary variable is out of range.

Check the Upper and Lower Range

 

 

 

 

Value

 

Span Too Small

 

The configured span is too small.

Check the Upper and Lower Range

 

 

 

 

Value.

 

Invalid Limits

 

The given Upper and Lower Sensor

Check that the difference between the

 

 

 

Limits are invalid.

Upper and Lower Sensor Limits is

 

 

 

 

greater than the Minimum Span.

7-41

Page 171
Image 171