Rosemount 5300 Series

Reference Manual

00809-0100-4530, Rev BA July 2009

Analog Output (HART)

9.Configure the Analog Output HART command: [2,1, 6].

Analog Output is not available for FOUNDATION Fieldbus.

Typically, the Primary Variable (PV) is configured to be Product Level, Interface Level, or Volume. Other variables like Product Distance, Interface Distance, Upper Product Thickness, etc. are available as well.

Specify the analog output range by setting the Lower Range Value (4 mA) and the Upper Range Value (20 mA) to the desired values.

The Alarm Mode specifies the output state when a measurement error occurs.

See also “Analog Output (HART)” on page 5-9for information on Analog Output configuration.

Finish Configuration

Wizard

10. Finish the Configuration Wizard

This is the last window in the Configuration Wizard concluding the basic configuration. The current configuration can be changed at any time by using the Setup windows (General, Tank, Output etc., see “Using the Setup Functions” on page 5-18).

The Setup windows contain further options not available in the configuration wizard.

Click the Finish button and continue with the next step in the Guided Setup.