Reference Manual

00809-0100-4530, Rev BA July 2009

Rosemount 5300 Series

7. Select the TRANSDUCER1100 block and choose the Geometry tab.

8.Tank Height is the distance from the Upper Reference Point to the tank bottom (see “Tank and Probe Geometry” on page 5-4). Make sure that this number is as accurate as possible.

9.Select the Mounting Type used.

10.Select Inner Diameter if using pipe, chamber, or nozzle.

11.Type Nozzle Height if using nozzle.

FOUNDATION Fieldbus parameter:

TRANSDUCER 1100>GEOM_TANK_HEIGHT

TRANSDUCER 1100>MOUNTING_TYPE

TRANSDUCER 1100>PIPE_DIAMETER

TRANSDUCER 1100>NOZZLE_HEIGHT

12. Select the Environment tab.

13.Normally, the Measurement Mode does not need to be changed. The transmitter is pre-configured according to the specified model.