WRITE PROTECTING A TRANSMITTER

A Rosemount 5300 Series transmitter can be protected from unintentional configuration changes by a password protected function. The default password is 12345. It is recommended that this password is not changed to facilitate service and maintenance of the transmitter.

RRM: Tools>Lock/Unlock Configuration Area.

AMS Suite: Tools>Service>Lock/Unlock Device.

HART Command: [3, 2, 1, 2].

DeltaV:

1.In the DeltaV Explorer, select the transmitter icon, and click the right mouse button on the Transducer 1100 block icon.

TRANSDUCER1100

Unlock/Lock

2.Choose the Unlock/Lock Device option.

ENTER SERVICE MODE IN RRM

In RRM, service functions for advanced users are available for the Rosemount 5300 Series transmitter. Setting RRM into Service Mode, all the Service menu options in RRM are enabled. The default password for enabling the Service Mode is “admin”. The password can be changed by selecting the Change Password option from the Service menu.