ANALOG OUTPUT CALIBRATION

This function lets you calibrate the Analog Output by comparing the actual output current with the nominal 4 mA and 20 mA currents. Calibration is done at the factory and normally the transmitter does not need to be recalibrated.

The Analog Output Calibration function is available via the HART command [2, 8, 1].

In RRM, this function is available via Setup>Output. To calibrate the Analog Output current:

1.Start RRM and make sure that the transmitter communicates with the PC (see Section 5: Basic Configuration Using Rosemount Radar Master).

2.Click the Output icon in the Device Config/Setup toolbar.

3.Select the Analog Out tab in the Output window.

4.Click the Calibrate DAC button.

5. Follow the instructions to calibrate the 4 mA and the 20 mA outputs.