BASIC CONFIGURATION PARAMETERS

Measurement Units

Tank and Probe

Geometry

Figure 5-1. Tank Geometry

Product Level

Interface

Level

This section describes basic configuration parameters for a Rosemount 5300 transmitter. Basic configuration is only needed for the 5300 Series transmitters which are not pre-configured at the factory. Factory configuration is normally specified in the Configuration Data Sheet.

Measurement units can be specified for presentation of Level/Interface Level, Level Rate, Volume, and Temperature values.

The basic transmitter configuration includes setting the tank geometry parameters.

Upper Reference Point

Hold Off/

Upper Null Zone

Probe

Tank Height

Length

 

 

 

 

 

 

Lower Reference Point

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 5-2. Upper Reference

For the different tank connections the Upper Reference Point is located at the

Point

underside of the threaded adapter or at the underside of the welded flange, as

 

 

illustrated in Figure 5-2:

Adapter

Upper Reference Point

NPT

BSP (G) Flange

Tri-Clamp

5-4

Page 76
Image 76