Reference Manual

00809-0100-4530, Rev BA July 2009

Rosemount 5300 Series

BASIC CONFIGURATION USING A 375 FIELD COMMUNICATOR

Figure 5-6. The 375 Field Communicator.

This section describes how to configure the 5300 transmitter by using a 375 Field Communicator.

The menu tree with the various configuration parameters is shown in Figure 5-7 on page 5-12. Section “Basic Configuration Parameters” on page 5-4presents a description of the basic configuration parameters.

For information on all the capabilities, refer to the 375 Field Communicator Product Manual (Document No. 00809-0100-4276).

Tab Key

Navigation Keys

Alphanumeric Keys

Enter Key

Function Key

Backlight adjustment key

1.Check that the desired Measurement Units are selected.

2.Open the Process Variable menu and select Primary Variable. HART command: [1,1]. Select the desired parameter.

3.Open the Basic Setup menu. HART command: [2, 1]. This menu includes Probe, Tank Geometry, Environment, Volume, and Analog Output settings.

4.Select Finish, Device Specific Setup to see if there is any additional configuration that needs to be done.

5.Restart the transmitter. HART command: [3, 2, 1, 1].

See also “Guided Setup” on page 5-19for further information on configuration of the Rosemount 5300 transmitter.