CONFIGURE THE AI BLOCK

A minimum of four parameters are required to configure the AI Block. The parameters are described below with example configurations shown at the end of this section.

CHANNEL

Select the channel that corresponds to the desired sensor measurement. The Rosemount 5300 measures Level (channel 1), Distance (channel 2), Level Rate (channel 3), Signal Strength (channel 4), Volume (channel 5), Internal Temperature (channel 6), Upper Product Volume (channel 7), Lower Product Volume (channel 8), Interface Distance (channel 9), Upper Product Thickness (channel 10), Interface Level (channel 11), Interface Level Rate (channel 12), Interface Signal Strength (channel 13), Signal Quality (channel 14), Surface/Noise Margin (channel 15), and Vapor DC (channel 16).

AI Block

TB Channel Value

Process Variable

Level

1

CHANNEL_RADAR_LEVEL

Ullage

2

CHANNEL_RADAR_ULLAGE

Level Rate

3

CHANNEL_RADAR_LEVELRATE

Signal Strength

4

CHANNEL_RADAR_SIGNAL_STRENGTH

Volume

5

CHANNEL_RADAR_VOLUME

Internal Temperature

6

CHANNEL_RADAR_INTERNAL_TEMPERATURE

Upper Product

7

CHANNEL_UPPER_PRODUCT_VOLUME

Volume

 

 

Lower Product

8

CHANNEL_LOWER_ PRODUCT_VOLUME

Volume

 

 

Interface Distance

9

CHANNEL_INTERFACE_ DISTANCE

Upper Product

10

CHANNEL_UPPER_ PRODUCT_THICKNESS

Thickness

 

 

Interface Level

11

CHANNEL_INTERFACE_LEVEL

Interface Level Rate

12

CHANNEL_INTERFACE_ LEVELRATE

Interface Signal

13

CHANNEL_INTERFACE_ SIGNALSTRENGTH

Strength

 

 

Signal Quality

14

CHANNEL_SIGNAL_QUALITY

Surface/Noise Margin

15

CHANNEL_ SURFACE_NOISE_MARGIN

Vapor DC

16

CHANNEL_VAPOR_DC

L_TYPE

The L_TYPE parameter defines the relationship of the transmitter measurement (Level, Distance, Level Rate, Signal Strength, Volume, and Average Temperature) to the desired output of the AI Block. The relationship can be direct or indirect root.

Direct

Select direct when the desired output will be the same as the transmitter measurement (Level, Distance, Level Rate, Signal Strength, Volume, and Internal Temperature).

Indirect

Select indirect when the desired output is a calculated measurement based on the transmitter measurement (Level, Distance, Level Rate, Signal Strength, Volume, and Internal Temperature). The relationship between the transmitter measurement and the calculated measurement will be linear.