Power Requirements

Terminals in the transmitter housing provide connections for signal cables.

 

The Rosemount 5300 transmitter is powered over FOUNDATION Fieldbus with

 

standard fielbus power supplies. The transmitter operates with the following

 

power supplies:

 

 

 

 

 

 

 

 

 

Approval Type

 

Power Supply (Vdc)

 

 

IS

9

- 30

 

 

 

 

 

 

Explosion-Proof/Flameproof

16 - 32

 

 

None

9

- 32

 

 

 

 

 

 

 

FISCO; IS

9

- 17.5

 

 

 

 

 

 

Connecting the Transmitter

To connect the transmitter:

1. Make sure the power supply is switched off.

2. Remove the terminal block cover.

3.Pull the cable through the cable gland/conduit. Install wiring with a drip loop. The bottom of the loop must be lower than the cable/conduit entry.

4.Connect wires according to Figure 4-9 for non-intrinsically safe power supplies, and according to Figure 4-10for intrinsically safe power supplies.

5.Use the enclosed metal plug to seal any unused port.

6. Mount the cover and tighten the cable gland making sure the cover is secure to meet explosion-proof requirements.

7.For ATEX, IECEx and NEPSI installations, lock the cover with the Locking Screw .

8.Connect the power supply.

NOTE!

Use PTFE tape or other sealant at the NPT threads in the Cable Entries.