Reference Manual

00809-0100-4530, Rev BA July 2009

Rosemount 5300 Series

AMS SUITE

Prior to this test, inspect the echo curve to ensure that no disturbing echoes affecting the measurement performance are present.

AMS: Click Configure / Setup / Echo Curve

1.Bypass the safety PLC or take other appropriate actions to avoid false trip.

2.Disable write protection if the function is enabled.

AMS: Select Device Diagnostics / Tools from the left menu.

Write Protect...

Click Write Protect... and follow the instructions. (Note that the password cannot be written with letters.)

3.Using loop test, enter the mA value representing the high alarm current. Verify that the analog output current is correct using the reference meter. This step tests for compliance voltage problems, such as low power supply voltage or increased wiring resistance.

AMS: Select Configure / Setup, Analog Output from the menu.

Loop Test...

Click Loop Test... Select Other and enter the mA value representing the high Analog Output Level and follow the instructions. Verify that the output current is correct.

E-5

Page 279
Image 279
Emerson Process Management 5300 manual AMS Suite, AMS Click Configure / Setup / Echo Curve, Write Protect