Application Example 3 Radar Level Transmitter, Product Level and Interface Level Value

A level transmitter is measuring the product level and the interface level in a 33 ft. (10 m) high tank. The maximum interface level is 10 ft. (3 m).

Figure 5-16. Situation Diagram

100%

10ft (3 m)

0%

100%

33ft

(10 m)

0%

Solution

Table 5-11. Analog Input Function Block Configuration for a Level and Interface Transmitter

Figure 5-17. Analog Input Function Block Diagram for a Level and Interface Transmitter

Table 5-11lists the appropriate configuration settings, and Figure 5-17illustrates the correct function block configuration.

 

 

 

 

AI Function Block Product Level

 

 

AI Function Block Interface Level

 

 

Parameter

 

Configured Values

 

Parameter

Configured Values

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L_TYPE

 

 

 

Direct

 

 

L_TYPE

Direct

 

XD_SCALE

 

 

 

Not Used

 

 

XD_SCALE

Not Used

 

OUT_SCALE

 

 

 

Not Used

 

 

OUT_SCALE

Not Used

 

 

CHANNEL

 

 

CH1: Level

 

 

CHANNEL

CH11: Interface Level

 

Level Measurement

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUT_D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AI Function Block

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUT

To Another

 

 

 

(Product Level)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Function Block

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Interface Level Measurement

 

 

 

 

 

 

 

 

 

 

 

 

OUT_D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AI Function Block

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUT

To Another

 

 

 

(Interface Level)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Function Block

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 