
Hazardous Area Oxymitter 4000
Instruction Manual
| 2. Additional IMPS 4000 Alarm Contacts. | |
a. If autocalibration is not utilized, a common | (a) | One contact per IMPS 4000 for |
| “low calibration gas flowing”. | |
any of the diagnostic alarms listed in Table |
|
|
(b) | One contact per IMPS 4000 for | |
actuate this contact can be modified to one |
| “high calibration gas flowing”. |
of seven additional groupings (mode 0 |
|
| |
through mode 7) listed in Table | NOTE |
| |
The logic contact is | The |
| |
with a 340 ohm series resistance. An inter- | to respond normally during any cali- |
| |
posing relay will be required if this contact is | bration, or can be configured to hold |
| |
to be utilized to annunciate a higher voltage | the last O2 value upon the initiation of |
| |
device, such as a light or horn. An inter- | calibration. Factory default is for the |
| |
posing relay may also be required for cer- |
| ||
tain DCS input cards. | throughout calibration. |
| |
A Potter & Brumfield | NOTE |
| |
mA DC or an equal interposing relay will be | Holding the last O2 value may be useful |
| |
mounted where the contact wires terminate |
| ||
in the control/relay room. | if several probes are being averaged |
| |
|
| for the purpose of automatic control. |
|
b. If autocalibration systems are utilized, the | Unless several probes are being aver- |
| |
aged, always place any control loops |
| ||
using the O2 signal into manual prior to |
| ||
bration system (SPS 4000 or IMPS 4000) | calibrating. |
| |
and is unavailable for alarming purposes. |
|
| |
The following additional contacts are pro- |
|
| |
vided through the autocalibration systems: |
| ||
1. SPS 4000 and IMPS 4000, | INDICATIONS |
| |
|
| ||
(a) | One contact closure per probe | For a Hazardous Area Oxymitter 4000 with a |
|
membrane keypad, faults are indicated by four |
| ||
| from the control room to the SPS |
| |
| diagnostic, or unit, alarm LEDs. A pattern of |
| |
| 4000 or IMPS 4000 for “calibration |
| |
| repeating blinks define the problem. A con- |
| |
| initiate”. |
| |
| densed table of the errors and the correspond- |
| |
(b) | One contact output per probe from | ing blink codes can be found on the inside right |
|
cover of the electronics housing. Table |
| ||
| |||
| the SPS 4000 or IMPS 4000 to the | identifies the blink code and fault status of each |
|
| control room for “in calibration” | LED as well as the output of the |
|
| notification. | line and a fault number that corresponds to the | 8 |
(c) One contact output per probe from | troubleshooting instructions provided in this |
| |
section. |
| ||
| the SPS 4000 or IMPS 4000 to the |
|
|
|
|
| |
| control room for “calibration failed” | For a Hazardous Area Oxymitter 4000 with the |
|
| notification. (Includes output from | optional LOI, alarm messages are displayed on |
|
| pressure switch indicating “cal gas | the LOI display window when the alarm status |
|
| bottles empty”). | display is accessed via the LOI menu. A listing |
|
of the alarm/fault messages and the related fault status descriptions and fault numbers are shown in Table
Rosemount Analytical Inc. A Division of Emerson Process Management | Troubleshooting |