If using an IMPS 4000 or an SPS 4000, install it in a
2.Calibration Handshake/Logic I/O. The output signal can be used to trigger an alarm or to provide a calibration hand- shake signal to an IMPS or SPS 4000.
If autocalibration is not utilized, a common
The logic contact is
+5 VDC, with a 340 ohm series resis- tance. An interposing relay is required if the logic contact will annunciate a higher voltage device, such as a light or horn. An interposing relay may also
be required for certain DCS input cards. A Potter & Brumfield model
equal) interposing relay will be2-4mounted where the contact wires
terminate in the control/relay room.
d.Install cover (17, Figure
e.Install Interconnecting Cable
NOTE
If interconnect cable was not purchased with the Hazardous Area Oxymitter 4000, consult the factory for the proper wire type and gauge.
1.Remove cover (17, Figure
If using an IMPS 4000 or an SPS 4000, install it in a
2.Loosen screw (18, Figure
3.See (Figure
4.Install covers (17, Figure
PNEUMATIC INSTALLATION
a.Reference Air Package
After the Hazardous Area Oxymitter 4000 is installed, connect the reference air set to the Hazardous Area Oxymitter 4000. Refer to Figure
Instrument Air (Reference Air): 68.95 kPa gage (10 psig) minimum, 1551.38 kPa gage (225 psig) maximum at 0.5 scfm (0.25 l/hr) maximum; less than 40