Instruction Manual
Hazardous Area Oxymitter 4000
c.Verify Hazardous Area Oxymitter 4000 Configuration
Located on the microprocessor board, the top board, are two switches that configure outputs for the Hazardous Area Oxymitter 4000 (Figure
The HART option is not protected by energy limiting barriers. It must not be interfaced from within the hazardous area. The
1.Hazardous Area Oxymitter 4000 status, HART or LOCAL.
2.Oxygen range, 0 to 10% O2 or 0 to 25% O2. (0 to 40% O2 is also configur- able only through HART/AMS.)
3.The
Remove power from the Hazardous Area Oxymitter 4000 before changing defaults. If defaults are changed under power, damage to the electronics package may occur.
d.SW1
The two settings are internally or externally powering the
e.SW2
The factory sets this switch as follows:
1.Position 1 is HART/LOCAL. This switch setting controls the configuration of the
Hazardous Area Oxymitter 4000. The defaults cannot be changed via
2.Position 2 determines the O2 range. This can be set to either 0 to 10% O2 or 0 to 25% O2. The factory setting is 0 to 10% O2.
Typically, the probe’s sensing cell, in direct contact with the process gases, is heated to approximately 736°C (1357°F). The external temperature of the probe body may exceed 450°C (842°F). If operating conditions also contain high oxygen levels and com- bustible gases, the Hazardous Area Oxymitter 4000 may
If necessary, the O2 range can be con- figured from 0 to 40% O2. To select values within this range, set SW2, position 1 to HART and then enter the range via HART/AMS. Do not change SW2, position 1 to LOCAL unless you want to operate in the range specified by SW2, position 2.
3.Position 3 determines the output at startup or at an alarm. The settings are 3.5 mA or 21.6 mA. The factory setting is 3.5 mA. At startup, the current at the analog output is 3.5 mA or 21.6 mA.
4.Position 4 can be used to set the heater for 115 or 220 Vac operation. This switch is functional only when the software is set for manual voltage selection (Auto Tune = No). Otherwise, the internal electronics auto detect the input line voltage and sets the heater voltage accordingly (Auto Tune = Yes).
f.Once the cell is up to operating tempera- ture, the O2 percentage can be read:
Rosemount Analytical Inc. A Division of Emerson Process Management |