Chapter 8. PROGRAM SETUP

Setting event items

Handling Precautions

Events assigned to the selected channel can be displayed.

Note that when setup data C57 is set to 1, event items on the programming map are skipped and not displayed.

When the event is a PV event

(1)In the set value display state, move to the segement event item to be set on the programming map.

(2)Press the ENTER key to make display panel 1 flash (registration of first setting).

(3)Use the , , , and keys to make the first setting – setting the event operating point.

Setting range : OFF –19999 to +20000 SPU

:OFF 0 to 20000 SPU (for absolute value deviation events)

:OFF –5.0 to +105.0% (for MV events)

(4)Press the ENTER key to stop the flashing on display panel 1. (Pressing the FUNC and CLR keys causes display panel 1 to return to unset state “-----” and the flashing stops.)

Display (PV events)

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

￿￿￿￿￿￿￿￿￿￿￿

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

Unset values are indicated as “ ----- ”.

NOTE

A PV event setting consists of a setting (including OFF) and a subfunction. A subfunction cannot be used when a setting has not been made “ ----- ”.

8-7