Chapter 4. WIRING

5-wire system RS-485 connection diagram

 

Slave station side DCP552

Terminating resistor

60

SDA

 

 

 

61SDB

Terminating resistor

62RDA

 

63RDB

 

64SG

Shield

 

FG

 

 

Master station

 

 

RDA

 

 

RDB

 

 

SDA

 

 

SDB

 

 

SG

 

 

FG

 

 

Shield

 

 

 

Slave station side DCP552

 

60SDA

 

61SDB

 

62RDA

 

63RDB

 

64SG

 

 

FG

Shield

 

 

 

Slave station side DCP552

 

60SDA

Terminating resistor

61SDB

62RDA

 

Terminating resistor

63RDB

64SG

 

 

 

FG

Attach 1/2W or greater terminating resistances of 150Ω ±5% at each end of the communications lines. Ground the shield FGs at one end in one location, not at both ends.