Chapter 8. PROGRAM SETUP

When the event is a timer code event

(1)In the set value display state, move to the event item to be set for the segment on the programming map.

(2)Press the ENTER key to make display panel 1 flash (registration of first setting).

(3)Use the , , , and keys to make the first setting (output code). Setting range:0 to 2n – 1

(n indicates the number of output points set in event configuration 1 auxiliary setting 1.)

(4)Press the ENTER key to stop the flashing on display panel 1 and display panel 2 starts flashing. (Start of second setting)

(Pressing the FUNC and CLR keys causes display panel 1 and 2 to return to unset state “-----” and the flashing stops.)

(5)Use the , , , and keys to make the second setting (time). Setting range: 0:00 to 500:00, 0.0 to 3000.0

(Time units are selected using setup data C64 to set Hour/min, Min/sec, 0.1 sec. Since a colon “: ” cannot be displayed, the decimal point is used instead.)

(6)Press the ENTER key to stop the flashing on display panel 2.

(Pressing the FUNC and CLR keys causes display panel 1 and 2 to return to unset state “-----” and the flashing stops.)

Display (Code event with a timer function)

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

Unset values are indicated as “-----”.

NOTE

Timer code events use one subfunction. A subfunction cannot be used when a setting has not been made “-----”.

Events that follow the event number of a timer code event (number of output points less 1) are skipped and not displayed.

8-10

Page 145
Image 145
Honeywell DCP552 Mark II user manual When the event is a timer code event, Display Code event with a timer function