DCP552 Parameter Work Sheet

No.

Item code

Item

Factory default

User

Settings and descriptions

 

 

 

settings

settings

 

 

 

 

 

 

 

36

PA 36

Group 3 delay time

0.0

 

0.0 to 3000.0sec

 

 

 

 

 

 

37

PA 37

Group 4 event number

0

 

0 to 16

 

 

 

 

 

(0: No delay is specified.)

 

 

 

 

 

 

38

PA 38

Group 4 delay time

0.0

 

0.0 to 3000.0sec

 

 

 

 

 

 

39

PA 39

FAST X

0

 

0 : 2 X

 

 

 

 

 

1 : 10 X

 

 

 

 

 

2 : 60 X

 

 

 

 

 

3 : 120 X

 

 

 

 

 

 

40

PA 40

CP computation for temperature

0

 

-1000 to +1000 PVU (CH1)

 

 

compensation

 

 

 

43

PA 43

PID operation initialize (CH1)

0

 

0 : No initialization during advance processing and PID

 

 

 

 

 

group change

 

 

 

 

 

1 : Initializes during advance processing but not during

 

 

 

 

 

PID group change.

 

 

 

 

 

2 : No initialization during advance processing but initializes

 

 

 

 

 

during PID group change.

 

 

 

 

 

3 : Initializes both during advance processing and PID

 

 

 

 

 

group change.

 

 

 

 

 

 

44

PA 44

PV2 message display mode

0

 

0 : CP or PO2 display

 

 

 

 

 

1 : mV value display

 

 

 

 

 

2 : O2 sensor impedance value display

45

PA 45

G.SOAK time (CH1)

2.0

 

0.1 to 60.0sec

 

 

 

 

 

 

46

PA 46

G.SOAK time (CH2)

2.0

 

0.1 to 60.0sec

 

 

 

 

 

 

51

PA 51

PV1 equalizer compensation point No. 1

Range lower

 

PV1 range lower limit value (tied)

 

 

 

limit value

 

 

 

 

 

 

 

 

52

PA 52

PV1 equalizer compensation amount No. 1

0 PVU

 

–1000 to +1000 PVU(PV1)

 

 

 

 

 

 

53

PA 53

PV1 equalizer compensation point No. 2

500 PVU

 

–19999 to +20000 PVU(PV1)

 

 

 

 

 

 

54

PA 54

PV1 equalizer compensation amount No. 2

0 PVU

 

–1000 to +1000 PVU(PV1)

 

 

 

 

 

 

55

PA 55

PV1 equalizer compensation point No. 3

1000 PVU

 

–19999 to +20000 PVU(PV1)

 

 

 

 

 

 

56

PA 56

PV1 equalizer compensation amount No. 3

0 PVU

 

–1000 to +1000 PVU(PV1)

 

 

 

 

 

 

57

PA 57

PV1 equalizer compensation point No. 4

1500 PVU

 

–19999 to +20000 PVU(PV1)

 

 

 

 

 

 

58

PA 58

PV1 equalizer compensation amount No. 4

0 PVU

 

–1000 to +1000 PVU(PV1)

 

 

 

 

 

 

59

PA 59

PV1 equalizer compensation point No. 5

2000 PVU

 

–19999 to +20000 PVU(PV1)

 

 

 

 

 

 

60

PA 60

PV1 equalizer compensation amount No. 5

0 PVU

 

–1000 to +1000 PVU(PV1)

 

 

 

 

 

 

61

PA 61

PV1 equalizer compensation point No. 6

2500 PVU

 

–19999 to +20000 PVU(PV1)

 

 

 

 

 

 

62

PA 62

PV1 equalizer compensation amount No. 6

0 PVU

 

–1000 to +1000 PVU(PV1)

 

 

 

 

 

 

63

PA 63

PV1 equalizer compensation point No. 7

3000 PVU

 

–19999 to +20000 PVU(PV1)

 

 

 

 

 

 

64

PA 64

PV1 equalizer compensation amount No. 7

0 PVU

 

–1000 to +1000 PVU(PV1)

 

 

 

 

 

 

65

PA 65

PV1 equalizer compensation point No. 8

3500 PVU

 

–19999 to +20000 PVU(PV1)

 

 

 

 

 

 

66

PA 66

PV1 equalizer compensation amount No. 8

0 PVU

 

–1000 to +1000 PVU(PV1)

 

 

 

 

 

 

67

PA 67

PV1 equalizer compensation point No. 9

4000 PVU

 

–19999 to +20000 PVU(PV1)

 

 

 

 

 

 

68

PA 68

PV1 equalizer compensation amount No. 9

0 PVU

 

–1000 to +1000 PVU(PV1)

 

 

 

 

 

 

69

PA 69

PV1 equalizer compensation point No. 10

Range lower

 

PV1 range upper limit value (tied)

 

 

 

limit value

 

 

 

 

 

 

 

 

70

PA 70

PV1 equalizer compensation amount No. 10

0 PVU

 

–1000 to +1000 PVU(PV1)

 

 

 

 

 

 

71

PA 71

PV2 equalizer compensation point No. 1

Low-limit value

 

PV2 range lower limit value (tied)

 

 

 

of range

 

 

 

 

 

 

 

 

72

PA 72

PV2 equalizer compensation amount No. 1

0 PVU

 

–1000 to +1000 PVU(PV2)

 

 

 

 

 

 

73

PA 73

PV2 equalizer compensation point No. 2

500 PVU

 

–19999 to +20000 PVU(PV2)

 

 

 

 

 

 

74

PA 74

PV2 equalizer compensation amount No. 2

0 PVU

 

–1000 to +1000 PVU(PV2)

 

 

 

 

 

 

75

PA 75

PV2 equalizer compensation point No. 3

1000 PVU

 

–19999 to +20000 PVU(PV2)

 

 

 

 

 

 

76

PA 76

PV2 equalizer compensation amount No. 3

0 PVU

 

–1000 to +1000 PVU(PV2)

 

 

 

 

 

 

77

PA 77

PV2 equalizer compensation point No. 4

1500 PVU

 

–19999 to +20000 PVU(PV2)

 

 

 

 

 

 

78

PA 78

PV2 equalizer compensation amount No. 4

0 PVU

 

–1000 to +1000 PVU(PV2)

 

 

 

 

 

 

denotes items settable only on models with CP compensation

2

Page 211
Image 211
Honeywell DCP552 Mark II user manual Denotes items settable only on models with CP compensation