DCP552 Parameter Work Sheet

 

User name

:

Preparation date

:

 

 

Equipment name

:

Product name

:

 

 

 

 

Model No.

:DCP552

Tag name

:

 

 

 

 

Instrumentation staffer in charge

:

Business staffer in charge

:

 

 

 

 

 

 

 

 

 

Variable parameter setting

No.

Item code

Item

Factory default

User

 

Settings and descriptions

 

 

 

settings

settings

 

 

 

 

 

 

 

 

 

1

PA 01

Key lock

0

 

0

: Keylock disabled

 

 

 

 

 

1

: Display of setup data settings disabled

 

 

 

 

 

2

: Display of all settings disabled

 

 

 

 

 

3

: Display of all settings disabled. Operation keys disabled.

 

 

 

 

 

 

 

2

PA 02

Memory protect

0

 

0

: Disabled

 

 

 

 

 

1

: Program settings are protected.

 

 

 

 

 

2

: Setup, variable parameters and event configuration

 

 

 

 

 

 

settings are protected.

 

 

 

 

 

3

: Setup, variable parameters, event configurations

 

 

 

 

 

 

and program settings are protected.

 

 

 

 

 

4

: Setup, variable parameters, event configurations

 

 

 

 

 

 

and PID parameter settings are protected.

 

 

 

 

 

5

: Program settings and all parameter settings are protected.

 

 

 

 

 

 

 

3

PA 03

Display channel setting

0

 

0

: 2 items are displayed for the selected CH

 

 

 

 

 

1

: Simultaneous 2CH display of the same item

 

 

 

 

 

 

 

4

PA 04

Synchronous 2 channel

0

 

0

: asynchronous

 

 

operation

 

 

1

: synchronous

 

 

 

 

 

 

 

5

PA 05

Program auto load

0

 

0

: OFF

 

 

 

 

 

1

: ON

 

 

 

 

 

 

 

8

PA 08

Auto-tuning (CH1)

0

 

0

: AT not performed

 

 

 

 

 

1

: Standard AT performed on currently used PID group

 

 

 

 

 

 

in mode other than READY mode

 

 

 

 

 

2

: AT writing overshoot-proof PID values to currently used

 

 

 

 

 

 

PID groups in mode other than READY mode performed

 

 

 

 

 

3

: Standard AT performed on PID groups A1 to A7 in

 

 

 

 

 

 

READY mode

 

 

 

 

 

4

: AT writing overshoot-proof PID values to PID groups

 

 

 

 

 

 

A1 to A7 in READY mode continuously performed

 

 

 

 

 

 

9

PA 09

Auto-tuning MV lower limit (CH1)

0.0

 

–5.0 to upper limit %

 

 

 

 

 

 

10

PA 10

Auto-tuning MV higher limit (CH1)

100.0

 

Lower limit to +105%

 

 

 

 

 

 

11

PA 11

SP bias (CH1)

0 SPU

 

–10000 to +10000 SPU (CH1)

 

 

 

 

 

 

12

PA 12

PV digital filter (CH1)

0.0

 

0.0 to 120.0sec

 

 

 

 

 

 

13

PA 13

PV bias (CH1)

0 PVU

 

–1000 to +1000 PVU(PV1)

 

 

 

 

 

 

14

PA 14

Manipulated variable deviation

110.0

 

0.1 to 110.0% OUT / 0.1sec

 

 

limit (CH1)

 

 

 

 

 

 

 

 

 

 

15

PA 15

Time proportional output cycle (CH1)

10

 

1 to 240sec

 

 

 

 

 

 

16

PA 16

On-off control differential (CH1)

50 SPU

 

0 to 1000 SPUm (CH1)

 

 

 

 

 

 

17

PA 17

PID computation initialize

0.0

 

–5.0 to +105.0%

 

 

manipulated variable (CH1)

 

 

 

 

 

 

 

 

 

 

21

PA 21

SP bias (CH2)

0

 

-10000 to +10000 SPU (CH2)

 

 

 

 

 

 

22

PA 22

PV digital filter (CH2)

0.0

 

0.0 to 120.0sec

 

 

 

 

 

 

23

PA 23

PV bias (CH2)

0 PVU

 

–1000 to +1000 PVU(PV2)

 

 

 

 

 

 

24

PA 24

Manipulated variable

110.0

 

0.1 to 110.0% OUT/0.1 sec

 

 

deviation limit (CH2)

 

 

 

 

 

 

 

 

 

 

25

PA 25

Time proportional output

10

 

1 to 240sec

 

 

cycle (CH2)

 

 

 

 

 

 

 

 

 

 

26

PA 26

ON-OFF control differential

50

 

0 to 1000 SPU (CH2)

 

 

(CH2)

 

 

 

 

 

 

 

 

 

 

27

PA 27

PID computation initialize

0.0

 

-5.0 to +105.0%

 

 

manipulated variable (CH2)

 

 

 

 

 

 

 

 

 

 

31

PA 31

Group 1 event number

0

 

0 to 16

 

 

 

 

 

(0: No delay is specified.)

 

 

 

 

 

 

32

PA 32

Group 1 delay time

0.0

 

0.0 to 3000.0sec

 

 

 

 

 

 

33

PA 33

Group 2 event number

0

 

0 to 16

 

 

 

 

 

(0: No delay is specified.)

 

 

 

 

 

 

34

PA 34

Group 2 delay time

0.0

 

0.0 to 3000.0sec

 

 

 

 

 

 

35

PA 35

Group 3 event number

0

 

0 to 16

 

 

 

 

 

(0: No delay is specified.)

 

 

 

 

 

 

 

1

Page 210
Image 210
Honeywell DCP552 Mark II user manual DCP552 Parameter Work Sheet, Variable parameter setting