DCP552 Parameter Work Sheet

No.

Item code

Item

Factory default

User

Settings and descriptions

 

 

 

settings

settings

 

 

 

 

 

 

 

72

tP-A3

Tuning point (PID group A3)

2500 SPU

 

–19999 to +20000 SPU

73

P-A4

Proportional band (PID group A4)

100.0

 

0.0 to 1000.0%

 

 

 

 

 

(0.0: On-off control)

 

 

 

 

 

 

74

I-A4

Integral time (PID group A4)

0

 

0 to 3600sec

 

 

 

 

 

(0: no integral operation)

 

 

 

 

 

 

75

d-A4

Derivative time (PID group A4)

0

 

0 to 1200sec

 

 

 

 

 

(0: no derivative operation)

 

 

 

 

 

 

76

rE-A4

Manual reset (PID group A4)

50.0

 

0.0 to 100.0%

 

 

 

 

 

 

77

CP-A4

Switching point (PID group A4)

4000 SPU

 

–19999 to +20000 SPU

 

 

 

 

 

 

78

tP-A4

Tuning point (PID group A4)

3500 SPU

 

–19999 to +20000 SPU

 

 

 

 

 

 

79

P-A5

Proportional band (PID group A5)

100.0

 

0.0 to 1000.0%

 

 

 

 

 

(0.0: On-off control)

 

 

 

 

 

 

80

I-A5

Integral time (PID group A5)

0

 

0 to 3600sec

 

 

 

 

 

(0: no integral operation)

 

 

 

 

 

 

81

d-A5

Derivative time (PID group A5)

0

 

0 to 1200sec

 

 

 

 

 

(0: no derivative operation)

 

 

 

 

 

 

82

rE-A5

Manual reset (PID group A5)

50.0

 

0.0 to 100.0%

 

 

 

 

 

 

83

CP-A5

Switching point (PID group A5)

5000 SPU

 

–19999 to +20000 SPU

 

 

 

 

 

 

84

tP-A5

Tuning point (PID group A5)

4500 SPU

 

–19999 to +20000 SPU

 

 

 

 

 

 

85

P-A6

Proportional band (PID group A6)

100.0

 

0.0 to 1000.0%

 

 

 

 

 

(0.0: On-off control)

 

 

 

 

 

 

86

I-A6

Integral time (PID group A6)

0

 

0 to 3600sec

 

 

 

 

 

(0: no integral operation)

 

 

 

 

 

 

87

d-A6

Derivative time (PID group A6)

0

 

0 to 1200sec

 

 

 

 

 

(0: no derivative operation)

 

 

 

 

 

 

88

rE-A6

Manual reset (PID group A6)

50.0

 

0.0 to 100.0%

 

 

 

 

 

 

89

CP-A6

Switching point (PID group A6)

6000 SPU

 

–19999 to +20000 SPU

 

 

 

 

 

 

90

tP-A6

Tuning point (PID group A6)

5500 SPU

 

–19999 to +20000 SPU

 

 

 

 

 

 

91

P-A7

Proportional band (PID group A7)

100.0

 

0.0 to 1000.0%

 

 

 

 

 

(0.0: On-off control)

 

 

 

 

 

 

92

I-A7

Integral time (PID group A7)

0

 

0 to 3600sec

 

 

 

 

 

(0: no integral operation)

 

 

 

 

 

 

93

d-A7

Derivative time (PID group A7)

0

 

0 to 1200sec

 

 

 

 

 

(0: no derivative operation)

 

 

 

 

 

 

94

rE-A7

Manual reset (PID group A7)

50.0

 

0.0 to 100.0%

 

 

 

 

 

 

95

CP-A7

Switching point (PID group A7)

20000SPU

 

20000 SPU (tied)

 

 

 

(fixed)

 

 

 

 

 

 

 

 

96

tP-A7

Tuning point (PID group A7)

6500 SPU

 

–19999 to +20000 SPU

 

 

 

 

 

 

The settings on this page are PID parameters for CH1

11

Page 220
Image 220
Honeywell DCP552 Mark II user manual CP-A4