Chapter 12. CALIBRATION

12 - 2 Calibration Procedures

Enter calibration mode

(1)Release keylock. (PARA PA01=0)

(2)Press DISP key to permit ordinary indication condition.

Change to READY (RUN and HLD are off) and AUTO (MAN off) modes. The following LEDs will illuminate after the above operations.

RUN LED is OFF HLD LED is OFF MAN LED is OFF

￿￿￿￿￿￿￿￿￿￿￿￿

￿￿￿￿￿￿￿￿￿￿￿￿

￿￿￿￿￿￿￿￿￿￿￿￿!"#￿￿￿￿￿$%

￿￿￿￿￿&￿￿&'(￿￿￿￿!"#￿$%

￿￿￿

￿￿￿￿￿￿￿ ￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

￿￿￿￿ ￿￿￿ ￿￿￿￿￿￿￿￿￿￿￿￿ ￿￿￿￿￿￿￿

￿￿￿￿￿￿￿￿￿￿

 

￿￿￿￿￿￿￿￿￿￿￿￿￿￿

￿￿￿￿

 

 

Figure 12-2.

(3)To enter calibration mode, hold down the FUNC key, and press SETUP key and ENTER key simultaneously.

The display will show the symbols described in Figure 12-3. If the indication is different, repeat the above procedure after pushing DISP key to refresh the display.

(4)To select individual calibration items, press , , , , keys to select the item by scrolling, then SETUP key, and ENTER key.

The order of calibration items is described in Table 12-2.

0.0.0.0.

 

 

 

00

00

￿￿￿

￿￿￿￿

￿￿￿￿￿￿￿

￿￿￿

 

 

￿￿￿

 

￿￿￿

 

￿￿￿￿￿￿￿

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

A.d.J.S.

 

￿￿￿￿￿￿￿￿￿￿

 

 

￿￿￿￿ ￿￿￿ ￿￿￿￿￿ ￿￿￿￿￿￿￿

 

￿￿￿￿￿￿￿￿￿￿

￿￿￿￿

 

￿￿￿￿

 

 

 

 

Figure 12-3.

12-7

Page 197
Image 197