Chapter 8. PROGRAM SETUP

Display items

Items displayed are shown in the figure below.

 

(￿￿￿￿￿￿￿￿￿￿

￿￿#

 

#

￿￿￿￿

￿￿￿￿￿￿￿!￿￿￿￿￿￿￿$

 

 

#￿￿￿￿￿￿￿￿￿￿￿$￿

￿￿￿￿￿￿￿￿￿￿￿￿￿￿"￿￿"￿￿￿￿￿￿￿￿￿$￿￿￿￿￿￿￿￿￿%￿￿"￿"￿￿￿￿￿￿￿￿￿￿￿￿￿￿

#￿￿￿￿￿￿￿￿￿￿￿￿￿$￿

￿￿

 

￿￿￿

 

￿!

 

 

 

 

 

 

￿￿￿￿￿￿￿

&"￿￿￿￿￿￿￿ '

￿#￿!

￿￿￿￿￿￿￿￿￿￿￿￿￿￿

 

 

￿"￿￿￿￿￿￿￿￿

 

￿"￿"￿￿￿￿￿￿￿￿￿￿￿￿"￿$

 

 

 

￿￿￿!￿￿￿￿￿￿￿￿￿￿

 

Setting pattern items

(1)In the set value display state, move to the segment pattern item to be set on the programming map.

(2)Press the ENTER key to make display panel 1 flash (registration of first setting).

(3)Use the , , , and keys to set the first setting (SP). Setting range: SP limit lower limit to upper limit

(SP limit is set using setup data C66, C67, C69 and C70.)

(4)Pressing the ENTER key stops display panel 1 from flashing and causes display panel 2 to start flashing. (This starts start registration of the second setting.) Instead of pressing the ENTER key, press the FUNC and ENTER keys to switch between RAMP types (selecting RAMP-X RAMP-T, or RAMP-X RAMP-E is made with setup data C61).

(5)Use the , , , and keys to make the second setting (time). Setting range: 0:00 to 500:00, 0.0 to 3000.0

(Time units are selected using setup data C62 to set Hour/min, Min/sec, 0.1 sec. Since a colon “: ” cannot be displayed, the decimal point is used instead.)

(6)Press the ENTER key to stop display panel 2 from flashing.