Chapter 12. CALIBRATION
●Writing into EEPROM
(1)Press SETUP key until the PROG/SEG display shows
(2)Scroll ↑, ↓, ←, →, keys to show (1.1.1.1.) on upper display.
(3)Press ENTER key.
■Current output calibration
Scroll ↑, ↓, ←, →, keys to show (6.0.6.6.) on the upper display, then press
ENTER key.
Connect the digital ammeter across terminals (See Figure
●OUT CH1 output calibration
(1)Press SETUP key until the PROG/SEG display shows
Scroll ↑, ↓, ←, →, keys until meter indicates 4.00mA, then press ENTER key.
(2)Press SETUP key until the PROG/SEG display shows
Scroll ↑, ↓, ←, →, keys until meter indicates 20.00mA, then press ENTER key.
●OUT CH2 output calibration
(1)Press SETUP key until the PROG/SEG display shows
Scroll ↑, ↓, ←, →, keys until meter indicates 4.00mA, then press ENTER key.
(2)Press SETUP key until the PROG/SEG display shows
Scroll ↑, ↓, ←, →, keys until meter indicates 20.00mA, then press ENTER key.
●AUX CH1 output calibration
(1)Press SETUP key until the PROG/SEG display shows
Scroll ↑, ↓, ←, →, keys until meter indicates 4.00mA, then press ENTER key.
(2)Press SETUP key until the PROG/SEG display shows
Scroll ↑, ↓, ←, →, keys until meter indicates 20.00mA, then press ENTER key.
●AUX CH2 output calibration
(1)Press SETUP key until the PROG/SEG display shows
Scroll ↑, ↓, ←, →, keys until meter indicates 4.00mA, then press ENTER key.
(2)Press SETUP key until the PROG/SEG display shows
Scroll ↑, ↓, ←, →, keys until meter indicates 20.00mA, then press ENTER key.