Chapter 4. WIRING

4 - 3 Making Terminal Connections

To connect a line to the terminals, use crimp-style solderless wire connectors that fit an M3.5 screw.

7.4

Handling Precautions

6.6 or less 7.3 or less

Unit : mm

¿3.7

•If the DCP552 is mounted in a location subject to noticeable vibration or impact, be sure to use round crimp-style solderless wire connectors to prevent lines from becoming disconnected from the terminals.

•Be careful not to allow any of the crimp-style solderless wire connectors to touch adjacent terminals or connectors.

•The terminal screws shall be tightened to 0.78 to 0.98 Nm torque.

4-4

Page 32
Image 32
Honeywell DCP552 Mark II user manual Making Terminal Connections