Chapter 5. FUNCTIONS

Code event

Several events are used as one group and the number of output points are output as one parallel code number. Assigning code numbers to event outputs has the same effect as increasing the number of physical output points.

•Code event

Set event type to code event and set the number of output points (1 to 8) in auxiliary setting 1. An output code value (0 to 255) can be set for each segment. A binary coded low-order bit for the set number of output points is output.

The previous setting is valid until the program reaches a segment with a new setting.

Note, however, that unless a setting is made in the first segment, the program will assume that a set value of 0 is set in the first segment.

Example: Setting a code event involving 3 output points in event 3

The table below shows the output state when a value of 3 is set in segment 2, a value of 6 is set in segment 4 and a value of 0 is set in segment 5.

Segment

1

2

3

4

5

 

 

 

 

 

 

Set value

Not set

3

Not set

6

0

 

 

 

 

 

 

Code value

 

 

 

 

 

OFF

ON

ON

OFF

OFF

1 in event 3

 

 

 

 

 

 

 

 

 

 

 

 

Code value

 

 

 

 

 

OFF

ON

ON

ON

OFF

2 in event 4

 

 

 

 

 

 

 

 

 

Code value

 

 

 

 

 

OFF

OFF

OFF

ON

OFF

4 in event 5

 

 

 

 

 

 

 

 

 

 

 

 

 

0

3

3

6

0

Output code

OFF,OFF,OFF

OFF,ON,ON

OFF,ON,ON

ON,ON,OFF

OFF,OFF,OFF

 

0, 0, 0

0, 1, 1

0, 1, 1

1, 1, 0

0 , 0, 0

 

 

 

 

 

 