Chapter 5. FUNCTIONS

Mode event

This event goes on or off depending on controller mode, alarm generation and other states.

It cannot be combined with the event standby function but with the on delay function. It does not set event set values (operating points) or hysteresis.

Basic operations

The following types are provided.

RUN + HOLD + END + FAST HOLD

READY + READY FAST END

G.SOAK wait

MANUAL

During auto-turning execution

FAST + READY FAST Console setting operation

RUN

ADV (advance)

Full alarm (logical OR) PV range alarm Instrument alarm

O2 sensor failure Battery voltage drop

The event goes on when the specified instrument state is reached and is off at other times.

Alarm

Alarms are of two types: PV range alarm group (alarm code number 01 to 04) and instrument alarm group (alarm code number 91 to 99 and battery voltage drop). When the event type is all alarm, the event goes on if one alarm occurs. When the event type is a PV range alarm, the event goes on if one alarm in the PV range alarm group goes on.

When the event type is an instrument alarm, the event goes on if one alarm in the instrument alarm group goes on.

ADV

When ADV (advance) is executed, the event goes on for 1 second. This function is valid during on delay.