Chapter 6. OPERATION

Read timing

SW1 to 8 and 15 to 16 timing

￿￿￿￿￿SW1￿￿￿￿￿￿￿to 8￿￿￿￿￿and 15 to 16￿￿are￿￿￿￿￿￿￿read according to the timing in the figure shown below.

(1) When the input changes from OFF to￿￿￿ON,￿￿￿￿￿￿￿reading starts within less than 0.2 seconds. ￿￿￿

(2) When the input changes from ON￿￿￿to OFF, reading starts within less than 0.2 seconds.

SW9 to 14 and RUN, FAST (READY FAST) timing

Selecting SW9 to 14 program numbers takes less than 0.4 seconds after a change in input status.

Thus the following timings (1) to r must be observed during RUN operations.

FAST (READY FAST) operations should follow the same timings.

 

 

 

(1)

Time from number selection to leading edge of the RUN signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: 0.4 seconds or more

(2)

Time from the leading edge of the RUN signal to number selection hold

 

 

 

 

 

 

 

 

 

 

 

 

 

: 0.2 seconds or more

(3)

Time from RUN signal OFF to leading edge of RUN signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: 0.2 seconds or more

(4)

Time from leading edge of RUN signal to RUN signal ON hold

 

 

￿￿￿￿ ￿￿￿￿

￿￿￿

 

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

:

 

0.4 seconds￿￿￿

or less

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

 

 

 

 

 

 

 

 

 

 

 

 

 

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

 

￿￿￿￿￿￿￿￿

￿￿￿￿￿￿￿￿￿￿￿￿￿

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

 

 

 

 

 

 

 

 

 

 

 

 

 

: 0.2 seconds or more

(5)

Time from entry of selected number to program number change

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: 0.4 seconds or less

(6)

Time from leading edge of RUN signal to start of RUN signal

 

 

 

￿￿￿￿￿￿￿￿￿￿￿￿￿

 

 

 

 

 

 

 

 

 

 

￿

￿￿￿￿￿￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

￿￿￿

 

 

 

￿￿￿￿￿￿￿￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

%￿￿￿

￿!"#$

 

 

 

 

 

 

 

 

 

￿￿￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Handling Precautions

To ensure correct operation, the above read timings should be regarded as minimum time settings in external switch operations.

6-15