Chapter 12. CALIBRATION
■Cold junction sensor calibration
Scroll ↑, ↓, ←, →, keys to show (2022) on upper display, then press ENTER
key.
●The cold junction input 0% (CH1)
(1)Press SETUP key until the PROG/SEG display shows
(2)Connect the millivolt source between
(3)Press ENTER key after display stabilizes, AD count is shown on lower display.
●The cold junction input 100% (CH1)
(1)Press SETUP key until the PROG/SEG display shows
(2)Connect the millivolt source between
(3)Press ENTER key after display stabilizes, AD count is shown on lower display.
●The cold junction AD count data (CH1)
(1)Press SETUP key until the PROG/SEG display shows
(2)Press ENTER key after display stabilizes, AD count is shown on lower display.
●The cold junction temperature data (CH1)
(1)Press SETUP key until the PROG/SEG display shows
(2)Connect the thermometer (55).
(3)Scroll ↑, ↓, ←, →, keys to set above temperature value.
(4)Press ENTER key.
●The cold junction input 0% (CH2)
(1)Press SETUP key until the PROG/SEG display shows
(2)Connect the millivolt source between
(3)Press ENTER key after display stabilizes, AD count is shown on lower display.
●The cold junction input 100% (CH2)
(1)Press SETUP key until the PROG/SEG display shows
(2)Connect the millivolt source between
(3)Press ENTER key after display stabilizes, AD count is shown on lower display.
●The cold junction AD count data (CH2)
(1)Press SETUP key until the PROG/SEG display shows
(2)Press ENTER key after display stabilizes, AD count is shown on lower display.
●The cold junction temperature data (CH2)
(1)Press SETUP key until the PROG/SEG display shows
(2)Connect the thermometer (58).
(3)Scroll ↑, ↓, ←, →, keys to set above temperature value.
(4)Press ENTER key.