Chapter 8. PROGRAM SETUP

Setting PID groups and output limiter group number items

(1)In the set value display state, move to the PID group, output limiter group number item to be set for the segment on the programming map.

(2)Press the ENTER key to make display panel 1 flash (registration of first setting).

(3)Use the , , , and keys to make the first setting (PID group number). Setting range: ON-OFF, PID 0 to 9, PID A

(4)Press the ENTER key to stop the flashing on display panel 1 and display panel 2 starts flashing. (Start of second setting)

(Pressing the FUNC and CLR keys causes display panel 1 and 2 to return to unset state “Pld 0/otL 0 ” and the flashing stops.)

(5)Use the , , , and keys to make the second setting (output limiter group number).

Setting range: 0 to 9

(6)Press the ENTER key to stop the flashing on display panel 2.

(Pressing the FUNC and CLR keys causes display panel 2 to return to unset state “Pld 0/otL 0 ” and the flashing stops.)

Display

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

Unset values are indicated as “Pld 0/otL 0 ”.

When setup data C58 is set to 1, PID groups, output limiter group number items are skipped and not displayed.

NOTE

When a PID group or output limiter group number is not 0 or both are something other than 0, they use a subfunction. A subfunction cannot be used when a setting has not been made “Pld 0/otL 0 ”.

Handling Precautions

When a set value for a PID group number is 0, it is a sequel to a PID number in a previous segment. When the set value for a PID group number in the first segment is 0, the set value is 1.

When a set value for an output limiter group number is 0, it is a sequel to an output limiter group number in a previous segment. When the set value for an output limiter group number in the first segment is 0, the set value is 1.

8-12

Page 147