DCP552 Parameter Work Sheet

No.

Item code

Item

Factory default

User

 

Settings and descriptions

 

 

 

settings

settings

 

 

 

 

 

 

 

 

34

C 34

Manipulated variable in PV

0.0

 

–5.0 to +105.0%

 

 

overrange (CH1)

 

 

 

 

 

 

 

 

 

 

 

35

C 35

MANUAL change mode (CH1)

0

 

0

: Smooth

 

 

 

 

 

1

: Preset

 

 

 

 

 

 

36

C 36

Preset MANUAL value (CH1)

0.0

 

–5.0 to +105.0%

 

 

 

 

 

 

 

37

C 37

End of operation (CH2)

0

 

0

: READY mode

 

 

 

 

 

1

: END mode

 

 

 

 

 

 

38

C 38

Manipulated variable in READY

0.0

 

-5.0 to +105.0%

 

 

mode (CH2)

 

 

 

 

 

 

 

 

 

 

 

39

C 39

Manipulated variable setting in

0

 

0

: No

 

 

PV overrange (CH2)

 

 

1

: Yes

 

 

 

 

 

 

40

C 40

Manipulated variable in PV

0.0

 

-5.0 to +105.0%

 

 

overrange (CH2)

 

 

 

 

 

 

 

 

 

 

 

41

C 41

Manual change mode (CH2)

0

 

0

: smooth

 

 

 

 

 

1

: preset

 

 

 

 

 

 

42

C 42

Preset MANUAL value (CH2)

0.0

 

-5.0 to +105.0%

 

 

 

 

 

 

43

C 43

Service interruption time when

0

 

0 to 3600sec

 

 

running can be continued

 

 

 

 

 

 

 

 

 

 

 

44

C 44

CP computation type

1

 

0

: oxygen pressure (PO2) computation

 

 

 

 

 

1

: CP computation for NKG sensor

 

 

 

 

 

2

: CP computation for Marathon monitors and Cambridge

 

 

 

 

 

 

sensors

 

 

 

 

 

3

: CP computation for Corning sensors

 

 

 

 

 

4

: CP computation for AACC sensors

 

 

 

 

 

5

: CP computation for Barber-Coleman sensors

 

 

 

 

 

6

: CP computation for Furnace Control sensors

45

C 45

Auxiliary output 1 type

0

 

0

: SP1

 

 

 

 

 

1

: PV1

 

 

 

 

 

2

: Deviation1 (DEV1)

 

 

 

 

 

3

: Manipulated variable 1 (MV1)

 

 

 

 

 

4

: SP2

 

 

 

 

 

5

: PV2

 

 

 

 

 

6

: Deviation 2 (DEV2)

 

 

 

 

 

7

: Manipulated variable 2 (MV2)

 

 

 

 

 

8

: O2 sensor mV input value

 

 

 

 

 

 

46

C 46

Auxiliary output 1 lower limit (4mA)

0 SPU

 

–19999 to +20000 SPU (C45 not equal to 3)

 

 

 

 

 

–1999.9 to +2000.0% (C45 set to 3)

 

 

 

 

 

 

47

C 47

Auxiliary output 1 upper limit (20mA)

10000 SPU

 

–19999 to +20000 SPU (C45 not equal to 3)

 

 

 

 

 

–1999.9 to +2000.0% (C45 set to 3)

 

 

 

 

 

 

 

48

C 48

Auxiliary output 2 type

0

 

0

: SP1

 

 

 

 

 

1

: PV1

 

 

 

 

 

2

: Deviation1 (DEV1)

 

 

 

 

 

3

: Manipulated variable 1 (MV1)

 

 

 

 

 

4

: SP2

 

 

 

 

 

5

: PV2

 

 

 

 

 

6

: Deviation 2 (DEV2)

 

 

 

 

 

7

: Manipulated variable 2 (MV2)

 

 

 

 

 

8

: O2 sensor mV input value

 

 

 

 

 

 

49

C 49

Auxiliary output 2 lower limit (4mA)

0 SPU

 

–19999 to +20000 SPU (C48 not equal to 3)

 

 

 

 

 

–1999.9 to +2000.0% (C48 set to 3)

 

 

 

 

 

 

50

C 50

Auxiliary output 2 upper limit (20mA)

10000 SPU

 

–19999 to +20000 SPU (C48 not equal to 3)

 

 

 

 

 

–1999.9 to +2000.0% (C48 set to 3)

 

 

 

 

 

 

 

57

C 57

Programming item

0

 

0

: Displayed

 

 

Event

 

 

1

: Not displayed

 

 

 

 

 

 

 

58

C 58

Programming item

0

 

0

: Displayed

 

 

PID group, output limiter group

 

 

1

: Not displayed

 

 

 

 

 

 

 

59

C 59

Programming item

0

 

0

: Displayed

 

 

G.SOAK, PV shift, repeat

 

 

1

: Not displayed

 

 

 

 

 

 

 

60

C 60

Programming item

0

 

0

: Displayed

 

 

PV start, cycle, pattern link

 

 

1

: Not displayed

denotes items settable only on models with CP compensation

16

Page 225
Image 225
Honeywell DCP552 Mark II user manual 19999 to +20000 SPU C45 not equal to