DCP552 Parameter Work Sheet

Setup data setting

No.

Item code

Item

Factory default

User

 

 

Settings and descriptions

 

 

 

settings

settings

 

 

 

 

 

 

 

 

 

 

1

C 01

PV1 range number

0

 

0 to 16

: Thermocouple

 

 

 

 

 

48 to 52 : Linear (DC current and DC voltage)

 

 

 

 

 

64 to 71 : Resistance temperature detector

 

 

 

 

 

96 to 103 : Resistance temperature detector

 

 

 

 

 

128 to 134 : Linear (DC current and DC voltage)

 

 

 

 

 

 

 

2

C 02

PV1 temperature unit

0

 

0

: Celsius (°C)

 

 

 

 

 

1

: Fahrenheit (°F)

 

 

 

 

 

 

 

3

C 03

PV1 decimal point position

1

 

0 to 2

 

 

 

 

 

 

 

 

4

C 04

PV1 linear decimal point position

1

 

0 to 4

 

 

 

 

 

 

 

5

C 05

PV1 linear range lower limit

0 PVU

 

–19999 to +20000 PVU(PV1)

 

 

 

 

 

 

6

C 06

PV1 linear range upper limit

10000 PVU

 

–19999 to +20000 PVU(PV1)

 

 

 

 

 

 

 

7

C 07

PV1 cold junction compensation

0

 

0

: Provided (Compensated inside the instrument)

 

 

 

 

 

1

: Not provided (Compensated outside the instrument)

 

 

 

 

 

 

 

8

C 08

PV1 root extraction

0

 

0

: Not provided

 

 

 

 

 

1

: Provided

 

 

 

 

 

 

9

C 09

PV1 root extraction dropout

0.2

 

0.2 to 10.0% (Ratio to input range)

 

 

 

 

 

 

10

C 10

PV1 cold junction bias

0.0

 

–1.0 to + 1.0°C

 

 

 

 

 

 

 

11

C 11

PV2 range number

0

 

0 to 16

: Thermocouple

 

 

 

 

 

48 to 52 : Linear (DC current and DC voltage)

 

 

 

 

 

64 to 71 : Resistance temperature detector

 

 

 

 

 

96 to 103 : Resistance temperature detector

 

 

 

 

 

128 to 134 : Linear (DC current and DC voltage)

 

 

 

 

 

135

: O2 sensor (CP)

 

 

 

 

 

 

 

12

C 12

PV2 temperature unit

0

 

0

: Celsius (°C)

 

 

 

 

 

1

: Fahrenheit (°F)

 

 

 

 

 

 

 

13

C 13

PV2 decimal point position

1

 

0 to 2

 

 

 

 

 

 

 

 

14

C 14

PV2 linear decimal point position

1

 

0 to 4

 

 

 

 

 

 

 

15

C 15

PV2 linear range lower limit

0 PVU

 

–19999 to +20000 PVU(PV2)

 

 

 

 

 

 

16

C 16

PV2 linear range upper limit

10000 PVU

 

–19999 to +20000 PVU(PV2)

 

 

 

 

 

 

 

17

C 17

PV2 cold junction compensation

0

 

0

: Provided (Compensated inside the instrument)

 

 

 

 

 

1

: Not provided (Compensated outside the instrument)

 

 

 

 

 

 

 

18

C 18

PV2 root extraction

0

 

0

: Not provided

 

 

 

 

 

1

: Provided

 

 

 

 

 

 

19

C 19

PV2 root extraction dropout

0.2

 

0.2 to 10.0% (Ratio to input range)

 

 

 

 

 

 

20

C 20

PV2 cold junction bias

0.0

 

–1.0 to + 1.0°C

 

 

 

 

 

 

 

21

C 21

Control output system (CH1)

1

 

1

: 5G output (Current proportional control output)

 

 

 

 

 

2

: 6D output (Voltage time proportional control output) system A

 

 

 

 

 

3

: 6D output (Voltage time proportional control output) system B

 

 

 

 

 

4

: 8D output (open collector time proportional control output) system A

 

 

 

 

 

5

: 8D output (open collector time proportional control output) system B

 

 

 

 

 

 

 

 

22

C 22

Control output system (CH2)

1

 

 

 

 

 

 

 

 

 

 

 

23

C 23

Control action (CH1)

0

 

0

: PID — A reverse operation

 

 

 

 

 

1

: PID — A normal operation

 

 

 

 

 

2

: PID — B reverse operation

 

 

 

 

 

3

: PID — B normal operation

 

 

 

 

 

 

 

 

24

C 24

Control action (CH2)

0

 

 

 

 

 

 

 

 

 

 

 

 

30

C 30

PV equalizer

0

 

0

: None

 

 

 

 

 

 

1

: PV1 only

 

 

 

 

 

2

: PV2 only

 

 

 

 

 

3

: Both PV1 and PV2

 

 

 

 

 

 

 

31

C 31

End of operation (CH1)

0

 

0

: READY mode

 

 

 

 

 

1

: END mode

 

 

 

 

 

 

32

C 32

Manipulated variable in READY

0.0

 

–5.0 to +105.0%

 

 

mode (CH1)

 

 

 

 

 

 

 

 

 

 

 

 

 

33

C 33

Manipulated variable setting

0

 

0

: No

 

 

 

in PV overrange (CH1)

 

 

1

: Yes

 

15

Page 224
Image 224