Chapter 4. WIRING

4 - 2 Recommended Cables

To perform thermocouple input, connect a thermocouple element to the terminals. When the wiring distance is long or when connecting the thermocouple without the element to the terminals, connect via shielded compensating lead wires.

NOTE

•For I/O other than thermocouple, use polyethylene insulated vinyl sheathed cable for JCS-364 shielded instruments or equivalent. (general name: twisted shielded cable for instrument use)

The following cables are recommended.

Fujikura

2-wire

IPEV-S-0.9mm21P

 

 

Cable Co.

3-wire

ITEV-S-0.9mm21T

 

 

 

Hitachi Cable

2-wire

KPEV-S-0.9mm21P

 

 

Co.

3-wire

KTEV-S-0.9mm21T

 

 

 

•A shielded multicore microphone cord (MVVS) may be used, if electromagnetic induction is comparatively low.

4-3

Page 31
Image 31
Honeywell DCP552 Mark II user manual Recommended Cables