Chapter 10. TROUBLESHOOTING

Alarm code display

The DCP552 is designed to alternate display of the following alarm codes and normal display items in one-second intervals on display panel 1 when input failures or instrument system failures are detected.

In cases of multiple alarm codes, display of the codes is alternated with normal display items, starting in order from the alarm code with the smallest number.

Alarm classification

 

PV range alarm group

: AL01 to AL04

 

Measuring instrument alarm group

: AL90 to AL99, and battery voltage drop

 

 

 

(In case of battery voltage drop, BAT LED

 

 

 

of the console is flickered.)

 

 

 

 

Alarm

Alarm name

Contents

Countermeasure

code

 

 

 

 

AL01

PV1 overrange

PV1 is more than 110%FS.

Check PV1.

 

 

 

 

AL02

PV1 underrange

PV1 is less than –10%FS.

 

 

 

 

 

AL03

PV2 overrange

PV2 is more than 110%FS.

Check PV2

 

 

 

 

AL04

PV2 underrange

PV2 is less than –10%FS.

 

 

 

 

 

AL90

Board configuration failure

Incorrect board configuration

Request the repair.

 

 

 

 

AL92

Adjustment value is abnormal.Analog input/output

Request the repair.

 

 

adjustment data were broken.

 

 

 

 

 

AL93

Setup data is abnormal. Setup data were broken.

Check the setup data, and reset

 

 

 

 

the data.

 

 

 

 

AL94

Variable parameter is abnormal. Variable parameter were

Check the variable parameter,

 

 

broken.

 

and reset the data.

 

 

 

 

AL95

PID parameter is abnormal.

PID parameter were broken.

Check the PID parameter,

 

(Fixed command control data is abnormal.)

 

 

and reset the data.

 

 

 

 

AL96

Program data is abnormal. Program data were broken.

Check the program data,

 

 

 

 

and reset the data.

 

 

 

 

AL97

Event configuration data

Event configuration data

Check the event configuration data,

 

is abnormal.

were broken.

 

and reset the data.

 

 

 

 

AL99

PROM is abnormal.

System program were corrupted.

Request the repair.

 

 

 

 

 

*1: When AL90 is generated, the alarm code stays on and continued operation is disabled.

*2: Data checks performed by AL93 and AL97 may fail to detect corrupted data. When this happens, the alarm can be turned off by entering normal data.