Power Supply Calculations | Calculating the System Current Draw |
5.3Calculating the System Current Draw
5.3.1 Overview
The control panel must be able to power all internal and external devices continuously during the
When calculating current draw and the battery size, note the following:
•‘Primary’ refers to the main power source for the control panel
•‘Secondary’ refers to the control panel’s backup batteries
•All currents are given in amperes (A). Table
TABLE
To convert... | Multiply | Example | ||
|
|
|
| |
Milliamperes (mA) to | mA x 0.001 | 3 mA x 0.001 = | 0.003A | |
amperes (A) | ||||
|
|
| ||
|
|
|
| |
Microamperes (µA) to | µA x 0.000001 | 300 µA x 0.000001 | = 0.0003 A | |
amperes (A) | ||||
|
|
| ||
|
|
|
|
5.3.2 How to Use Table
Use Table
1.Enter the quantity of devices in all three columns
2.Enter the current draw where required. Refer to the Device Compatibility Document for compatible devices and their current draw
3.Calculate the current draws for each in all columns
4.Sum the total current for each column
5.Copy the totals from Column 2 and Column 3 to Table
Following are the types of current that can be entered into Table
Calculation Column 1 - The primary supply current load that the control panel must support during a
Calculation Column 2 - The primary supply current load that the control panel must support during a fire alarm condition, with AC power applied.
Calculation Column 3 - The standby current drawn from the batteries in a
100 |