Output Circuits | Installation |
2.4Output Circuits
2.4.1Outputs/Notification Appliance/Releasing Circuits
Each of the four Style Y (Class B) Notification Appliance Circuits can output a maximum of 3.0 amps of current. Total current drawn from these as well as other DC power outputs cannot exceed
7.0amps (refer to battery calculations section). Each circuit is supervised,
The NACs can be converted to Style Z (Class A) by installing two optional Class A Converter module. Refer to
Class B Notification Appliance Circuits (supervised and
4.7 KΩ, ½ watt resistor P/N:71252
Polarized Bell | Polarized Bell |
Polarized Strobe | Polarized Strobe |
Polarized Horn | Polarized Horn |
|
| Releasing Solenoid | Dummy load any unused |
|
|
| |
|
| Notification Appliance Circuits | circuits (P/N: 71245) |
|
|
| |
|
| polarity shown in alarm condition |
|
Ferrite Beads |
| Ferrite Bead | + - + - |
P/N 29150 | + - + - | P/N 29150 | |
|
|
| rp2001nac.cdr |
|
| Note: Short Circuit Supervision must be enabled when using the | |
|
| ||
|
| "Release Circuit 1 or Release Circuit 2" on page 58 for information | |
|
| on enabling short circuit supervision. |
|
Ferrite Bead (P/N 29150)
Large gauge wire should be looped through bead at least once as illustrated. Smaller gauge wire can be looped more often.
Ferrite Bead in open position | Ferrite Bead in closed position |
Figure 2.7 NAC/Output Connections