Product Description

Controls and Indicators

Special Application Resettable or Nonresettable Power - TB9

Operating Voltage: Nominal 24 VDC

Maximum Available Current: 500 mA (see note 1)

Power-limited Circuitry

Jumper selectable by JP31 for resettable or nonresettable power:

Jumper pins 1 & 2 on JP31 for nonresettable power

Jumper pins 2 & 3 on JP31 for resettable power

Refer to the Device Compatibility Document for compatible listed devices

1.3 Controls and Indicators

LCD Display

The FACP uses an 80-character

(4 lines X 20 characters) high viewing angle LCD display. The display includes a long life LED backlight that remains illuminated. If AC power is lost and the system is not in alarm, the LED backlight will turn off to conserve batteries.

SYSTEM ALL NORMAL

10:00A 012106

Key Panel

Mounted on the main circuit board, the key panel includes a window for the LCD display and indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25 keys, including a 16 key alpha-numeric pad similar to a telephone keypad.

Function keys:

Acknowledge/Step

Alarm Silence

Drill

 

• System Reset (lamp test)

 

Service/program keys:

 

• Keys labeled 1 to 9

 

* key

 

# key

Figure 1.1 Membrane/Display Panel

0 (recall) key

 

1st Event key

Clear key

Escape key

Mode key

Four cursor keys (up, down, left and right)

Enter key

MRP2001kypd.cdr

14