Product Description | Controls and Indicators |
Special Application Resettable or Nonresettable Power - TB9
Operating Voltage: Nominal 24 VDC
Maximum Available Current: 500 mA (see note 1)
Jumper selectable by JP31 for resettable or nonresettable power:
Jumper pins 1 & 2 on JP31 for nonresettable power
Jumper pins 2 & 3 on JP31 for resettable power
Refer to the Device Compatibility Document for compatible listed devices
1.3 Controls and Indicators
LCD Display
The FACP uses an
(4 lines X 20 characters) high viewing angle LCD display. The display includes a long life LED backlight that remains illuminated. If AC power is lost and the system is not in alarm, the LED backlight will turn off to conserve batteries.
SYSTEM ALL NORMAL
10:00A 012106
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25 keys, including a 16 key
Function keys:
•Acknowledge/Step
•Alarm Silence
• | Drill |
| |
• System Reset (lamp test) |
| ||
Service/program keys: |
| ||
• Keys labeled 1 to 9 |
| ||
• | * key |
| |
• | # key | Figure 1.1 Membrane/Display Panel | |
• | 0 (recall) key | ||
|
•1st Event key
•Clear key
•Escape key
•Mode key
•Four cursor keys (up, down, left and right)
•Enter key
MRP2001kypd.cdr
14 |