Circuit Mapping and |
Using the OUTPUT CIRCUITS menus, this fire panel will allow you to assign a release circuit type of operation to any two of the four output circuits. Up to two releasing circuits (or hazards), called RELEASE 1 and RELEASE 2, may be created. Input zones may be assigned in various ways to activate either one or both of the release circuits. The fire panel treats RELEASE 1 and RELEASE 2 functions independently from each other, although they may share input circuits for activation.
Example 3: A single hazard,
•Output Circuit 1 is programmed as alarm NAC using the OUTPUT CIRCUITS menus.
•Output Circuit 2 is programmed as Release Circuit 1 using the OUTPUT CIRCUITS menus.
•Output Circuit 3 is programmed as alarm NAC using the OUTPUT CIRCUITS menus
•Output Circuit 4 is programmed as supervisory NAC using the OUTPUT CIRCUITS menus.
•Either of smoke detector Input Zones 1 or 2 will directly activate Output Circuit 1 (Alarm NAC).
•Smoke detector Input Zone 2 will also directly activate Output Circuit 3 (Alarm NAC) but not Output Circuits 2 or 4.
•Smoke detector Input Zones 1 and 2 are
ZONE 1 TYPE 1=COMBO
2=COMBO W/AR. SUPERV
ZONE 2 TYPE 1=COMBO
2=COMBO W/AR. SUPERV
OUTPUT MAP ZONE 1
| 1=ALARM NAC | YES |
| 2=RELEASE 1 | YES |
| 3=ALARM NAC | NO |
|
| |
|
| |
| OUTPUT MAP ZONE 1 | |
| 1=SUPV BELL NAC | N/A |
|
|
|
REL 1 CROSS GROUP 1
1=ZONE 1 | YES |
2=ZONE 2 | YES |
3=ZONE 3 | NO |
OUTPUT MAP ZONE 2
| 1=ALARM NAC | YES |
| 2=RELEASE 1 | YES |
| 3=ALARM NAC | YES |
|
| |
|
|
|
| OUTPUT MAP ZONE 2 | |
| 1=SUPV BELL NAC | N/A |
|
|
|
105 |