Installation | ANN-BUS Devices |
2.7.9 ANN-RLY Relay ModuleThe ANN-RLY relay module provides 10 programmable Form-C relays when used with a compatible FACP.
2.7.9.1 ANN-RLY Board Layout
Figure 2.22 illustrates the ANN-RLY board showing locations of screw terminals for connection to the FACP and the DIP switches for selecting the ANN-BUS ID number.
ANN-BUS (ID#)
Address DIP switch
ANN-BUS Connector
Figure 2.24 ANN-RLY Board Layout
2.7.9.2Specifications
•Operating Voltage: 24 VDC
•Max. Current:
Alarm: 75 mA
Standby: 15 mA
•Relay Contact Ratings:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
•Operating Temperature: 32o F to 120o F (0o C to 49o C)
•For indoor use in a dry location only
2.7.9.3Mounting/Installation
The ANN-RLY relay module can be mounted inside the FACP main circuit board chassis.
44 | MRP-2001 & MRP-2001E PN 53040:A 4/16/2007 |