Programming

Master Programming Level

3.5.3.4 Auto Silence

The Auto Silence feature, when enabled, automatically silences all main circuit board silenceable notification appliances after a programmed length of time. To enable this feature and program the time delay before Auto Silence activation, press 2 while viewing Output Screen #2. The following screens will be displayed:

OUTPUT #

1=SILENCEABLE YES 2=AUTO SILENCE NO 3=SIL INHIBITED NO

Output Screen #2

AUTO SILENCE 1=NO2=5 MINUTES 3=10 MINUTES

Auto Silence Screen #1

AUTO SILENCE 1=15 MINUTES 2=20 MINUTES 3=25 MINUTES

Auto Silence Screen #2

AUTO SILENCE 1=30 MINUTES

Auto Silence Screen #3

To disable the Auto Silence feature, press 1 for No while viewing Auto Silence Screen #1. To enable the Auto Silence feature, press the number corresponding to the time delay which will elapse before Auto Silence activates. This information will be stored in memory and the display will return to NAC Screen #1.

Note: If the Output Circuit has been programmed as a Releasing Circuit, the Auto Silence Option will not be available and the display will indicate N/A next to it.

3.5.3.5 Silence Inhibited

The Silence Inhibit feature, when enabled, prevents the silencing of the selected main circuit board Output for a period of one minute. Resetting the FACP will also be prevented for one minute while the Output programmed for silence inhibit is activated. Pressing 3 while viewing Output Screen #2 will cause a screen to be displayed with the options 1=No Silence Inhibit and 2=1 Min. Silence Inhibit. Pressing 1 will disable the Silence Inhibit feature while pressing 2 will enable a 1 minute Silence Inhibit for the selected Output.