Template 9: Dual Hazard - Combined ReleaseFACP Configuration Templates

B.3 Template 9: Dual Hazard - Combined Release

TEMPLATE 9: DUAL HAZARD - COMBINED RELEASE

 

 

 

 

INPUT ZONES

 

 

 

 

 

1

2

3

4

5

6

OUTPUT CIRCUITS

 

2-WIRE SMOKE

FIRE

WATERFLOW

MANUAL

PULL

SUPV.

 

 

 

 

 

RELEASE

STATION

 

#1 ALARM NAC

 

X

X

X

X

X

 

#2 SUPV BELL NAC

 

 

 

 

 

 

X

#3 RELEASE SOLENOID 1

 

X

X

 

X

X

 

#4 RELEASE SOLENOID 2

 

X

X

 

X

X

 

Table Legend:

X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on corresponding output circuit).

Input Zone Types:

Zone 1 = 2-wire smoke

Zone 2 = Fire

Zone 3 = Waterflow - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)

Zone 4 = Manual Release

Zone 5 = Pull Station

Zone 6 = Supervisory

Output Circuit Types:

Output 1 = Alarm NAC

Output 2 = Supervisory Bell NAC

Output 3 = Release Solenoid 1 (unsupervised for shorts)

Output 4 = Release Solenoid 2 (unsupervised for shorts)

Timers

Soak Timer 1 - set for 10 minutes

Soak Timer 2 - set for 10 minutes

Waterflow Delay Timer - set for 10 seconds

AC Loss Delay Timer - set for 2 hours

Operation

Activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 4 (Manual Release) or Zone 5 (Pull Station) will operate the Alarm NAC Output #1, Release Solenoid 1 Output #3 and Release Solenoid 2 Output #4. Release Solenoid 1 will turn off water release following time-out of the 10 minute Soak Timer 1 and Release Solenoid 2 will turn off water release following time-out of the 10 minute Soak Timer 2

Activation of Input Zone 3 (Waterflow) will operate the Alarm NAC Output #1. There is a 10 second FACP initiated delay in activation since Waterflow Delay Timer is set to 10 seconds

Activation of Input Zone 6 (Supervisory) will operate the Supervisory Bell NAC Output #2

FACP Relay Operation

The following description of FACP relay operations are in addition to normal system operation.

Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3 (Waterflow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull Station) will operate Alarm Relay

Trouble Relay - any system trouble will activate the Trouble Relay

Supervisory - activation of Zone 6 (Supervisory) will operate the Supervisory Relay

MRP-2001 & MRP-2001E PN 53040:A 4/16/2007