Circuit Mapping and Cross-Zoning

Input-to-Output Circuit Mapping and Cross-Zone Operation

Example 4: A dual hazard, cross-zoned application using four input zones and two releasing output circuits. Input Zones 1 and 2 are cross-zoned to activate Output Circuit 2, which is programmed as RELEASE 1. Input Zones 3 and 4 are cross-zoned to activate Output Circuit 3, which is programmed as a RELEASE 2.

Output Circuit 1 is programmed as alarm NAC using the OUTPUT CIRCUITS menus.

Output Circuit 2 is programmed as Release Circuit 1 using the OUTPUT CIRCUITS menus.

Output Circuit 3 is programmed as Release Circuit 2 using the OUTPUT CIRCUITS menus

Output Circuit 4 is programmed as supervisory NAC using the OUTPUT CIRCUITS menus.

Any of smoke detector Input Zones 1 through 4 will directly activate Output Circuit 1 (Alarm NAC) but not Output Circuits 2, 3 or 4.

Smoke detector Input Zones 1 and 2 are cross-zoned (both must be in alarm) to activate Output Circuit 2 (Release 1) but not Output Circuits 3 or 4.

Smoke detector Input Zones 3 and 4 are cross-zoned (both must be in alarm) to activate Output Circuit 3 (Release 2) but not Output Circuits 2 or 4.

ZONE 1 TYPE 1=COMBO

2=COMBO W/AR. SUPERV

3=2-WIRE SMOKE

ZONE 2 TYPE 1=COMBO

2=COMBO W/AR. SUPERV

3=2-WIRE SMOKE

OUTPUT MAP ZONE 1

 

1=ALARM NAC

YES

 

2=RELEASE 1

YES

 

3=RELEASE 2

NO

 

 

 

 

 

OUTPUT MAP ZONE 1

 

1=SUPV BELL NAC

N/A

 

 

 

OUTPUT MAP ZONE 3

1=ALARM NAC

YES

2=RELEASE 1

NO

3=RELEASE 2

YES

 

 

OUTPUT MAP ZONE 3

1=SUPV BELL NAC

N/A

 

 

REL 1 CROSS GROUP 1

1=ZONE 1

YES

2=ZONE 2

YES

3=ZONE 3

NO

ZONE 3 TYPE 1=COMBO

2=COMBO W/AR. SUPERV

3=2-WIRE SMOKE

ZONE 4 TYPE 1=COMBO

2=COMBO W/AR. SUPERV

3=2-WIRE SMOKE

OUTPUT MAP ZONE 2

 

1=ALARM NAC

YES

 

2=RELEASE 1

YES

 

3=RELEASE 2

NO

 

 

 

 

 

 

OUTPUT MAP ZONE 2

 

1=SUPV BELL NAC

N/A

 

 

 

OUTPUT MAP ZONE 4

1=ALARM NAC

YES

2=RELEASE 1

NO

3=RELEASE 2

YES

 

 

 

OUTPUT MAP ZONE 4

1=SUPV BELL NAC

N/A

 

 

REL 2 CROSS GROUP 1

1=ZONE 1

NO

2=ZONE 2

NO

3=ZONE 3

YES

 

 

REL 2 CROSS GROUP 1

1=ZONE 4

YES

2=ZONE 5

NO

3=ZONE 6

NO

 

 

106

MRP-2001 & MRP-2001E PN 53040:A 4/16/2007