Master Programming Level | Programming |
Output Circuit MAP
INPUT ZONE # 1=ENABLED 2=TYPE
3=OUTPUT CIRCUIT MAP
Edit Input Zone Screen #2
INPUT ZONE #
1=NOUN/ADJECTIVE
2=DESCRIPTION
*****************
Edit Input Zone Screen #3
Output Mapping (per input zone) allows the programmer/operator to assign the Output Circuits that will be activated when a particular Input Zone or
As an example, if Template 6 has been selected as the FACP Configuration [refer to "FACP CONFIG (Application Templates)" on page 50], selecting the Output Circuit Map for Input Zone 1 will display the following screens:
OUTPUT MAP ZONE 1
1=ALARM NAC | YES | |
2=WATERFLOW NAC | NO | |
3=RELEASE 1 | YES | |
|
|
|
Output Map Screen#1 |
|
|
|
| |
OUTPUT MAP ZONE 1 |
| |
4=SUPV BELL NAC | N/A |
|
|
|
|
Output Zone Screen#2
The screens indicate that when Input Zone 1 is activated:
Output Circuit #1 default programmed as Alarm NAC will activate (Yes) Output Circuit #2 default programmed as Waterflow NAC will not activate (No) Output Circuit #3 default programmed as Release 1 will activate (Yes)
Output Circuit #4 default programmed as Supv Bell NAC is not mapped (N/A)
Note that the MAP may indicate that an Input Zone is programmed to a particular Output Circuit but, if it is
The Output Circuit Map can be customized by selecting or deselecting any of the four output circuits for activation. Pressing the number key corresponding to the selected output will toggle the display between Yes for activation by the Input Zone to No for no activation. The new customized programming is automatically saved by the panel as soon as it is entered.
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors about the detector currently being programmed. Pressing 1 while viewing Edit Input Zone Screen #3 will cause the following screen to be displayed:
Noun/Adjective Screen
53 |