ANN-BUS Devices | Installation |
2.7.6 ANN-S/PG Serial/Parallel Printer Interface InstallationThe ANN-S/PG Serial/Parallel Interface module allows the ancillary connection of a serial or parallel printer to the FACP for a real-time log of system events, detector status reports and event history. Note that either a serial or parallel printer may be installed, not both. Proceed with the installation as described in the following:
1.Ensure that all power (AC and DC) has been removed from the FACP.
2.Connect the ANN-S/PG to the FACP as illustrated in Figure 2.18
TB3
FACP
ANN-S/PG Module
ANN-BUS and power wiring are supervised and power-limited
Figure 2.18 ANN-S/PG Connection to FACP
Parallel
Cable Connectors for connection to
printer
Serial
3.Using the DIP switches on the back of the ANN-S/PG module, assign an ID number (address) to the module
4.Select the address and configuration options for the ANN-S/PG module as described in the Programming section of this manual (refer to "ANN-BUS" on page 71)
Note that the Auto-configure feature allows the programmer to quickly bring all installed ANN-BUS modules online (refer to "Auto-Configure" on page 73)
5.Connect a printer to the ANN-S/PG Parallel or Serial connector (refer to Figure 2.18 on page 37)
2.7.6.1Specifications
•Operating Voltage: 24 VDC
•Current (Alarm and Standby): 45 mA
•Ambient Temperature: 32oF to 120oF (0oC to 49oC)
•Max. Wiring Distance from FACP: 6,000 ft. (1,800 m)
•Mounting: Surface
•Dimensions: 6”W x 7-3/4”H x 1-7/16”D (15.2 cm W x 19.7 cm H x 3.7 cm D)
•For indoor use in a dry location only
2.7.6.2 PRN-6 Printer Installation
When connected to the FACP via the ANN-S/PG module, the PRN-6 prints the status changes within the control panel and time-stamps the printout with the time of day and date that the event occurred. It provides 80 columns of data on standard 9” x 11” tractor-feed paper. This section contains information on connecting a printer to the control panel and setting the printer options.
MRP-2001 & MRP-2001E PN 53040:A 4/16/2007 | 37 |